Mitsubishi F940GOT-SWD-E Operation Manual page 266

Graphic operation terminals melsec-got
Hide thumbs Also See for F940GOT-SWD-E:
Table of Contents

Advertisement

Graphic Operation Terminal F940GOT
1) Number
Enter the number of devices to which the data in the GOT is to be transferred.
The number of devices (1 to 4,000) set for the recipe No. 1 is used for all other recipes start-
ing from the recipe No. 2.
2) EDIT key (for detailed setting)
This key allows to set each recipe file in details.
1 Contents of operation
Set 2) Recipe Name, 3) Device and 4) Number.
2 Read trigger
When a specified bit device becomes ON or OFF, the contents of word devices starting
from the one set in 3) Device as many as the number set in 4) Number are transferred to
the memory built in the GOT.
3 Write trigger
When a specified bit device becomes ON or OFF, the data set in "4 Receipt device" are
transferred to word devices starting from the one set in 3] Device.
4 Recipe device
Enter the value of a device to be written to the PLC.
When data is read using "2 Read trigger", this value is overwritten by the read value.
*1 The write trigger cannot be omitted. The read trigger can be omitted when read is not
required.
Creation of Display Screen (SW¨ ¨ ¨ ¨ D5C-GOTRE-PACK) 12
12-38

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

F940got-lwd-e

Table of Contents