Graphic Operation Terminal F940GOT
14.3

Connection to PC manufactured by Allen-Bradley

When connecting the SLC500 Series PC manufactured by Allen-Bradley, set the communica-
tion parameters and the RS-232C port as follows using an SLC500 Series peripheral tool.
For connection, refer to the hardware manual of the GOT main unit and the instruction manual
of the SLC500 Series.
14.3.1

Setting of communication

• Setting of RS-232C (channel 0) parameters
Set the system mode driver (DF1) to "half-duplex slave (DF1)".
Set other parameters to default values (initial values).
• Channel configuration of DF1 (half duplex slave)
Set the parameters as shown in the table below.
Set all parameters except shaded ones to default values.
Diagnostic File
Baud Rale
Parity
Duplicate Packet Delection
Station Adress
Error Delection
Poll Timeout
RTS Off Delay
RTS Send Delay
Message Retries
Control Line
EOT Suppression
• Setting on GOT
When the connected PC is set to "SLC500 Series" in the screen creation software or "SET-
UP MODE" in the GOT, the following setting is selected.
(The following setting is automatically selected when the PC model is set to "SLC500
Series". You do not have to set them manually.)
Baud rate
Data length
Stop bit
Parity bit
Control method
Parameter
Additional Functions (in Ver. 3.00 or Later) 14
Set value
-
19200
Even
Disabled
0
BCC
50
0
0
3
No Handshaking
No
19200
8 bits
1 bit
Even
None
14-7