Connection Of Sysmac C Series - Mitsubishi F940GOT-SWD-E Operation Manual

Graphic operation terminals melsec-got
Hide thumbs Also See for F940GOT-SWD-E:
Table of Contents

Advertisement

Graphic Operation Terminal F940GOT
1.6.4

Connection of SYSMAC C Series

When the GOT is connected to the SYSMAC C Series PLC manufactured by OMRON, the fol-
lowing setting is required.
• Setting of host link unit
Set the communication format of the host link unit as shown below.
Used port
Transmission
speed
Data bit
Stop bit
Parity bit
Communication
mode
Command level
Procedure
Unit No.
* Only a model in which these set items are offered can be connected to the GOT.
*1 The GOT station No. can be set in "SET-UP MODE" (Refer to Paragraph 2.2.).
Setting example: Set the communication format while referring to setting examples of each
- In the case of CQM1-CPU . . . Setting by data memory (DM)
Set item
Standard communication con-
dition
(RS232C: DM6645)
Communication condition
(RS232C: DM6646)
Send delay time
(RS-232C: DM6647)
Unit No.
(RS-232C: DM6648)
When RS-422 is used
00 to 15 (BCD) (in accordance with setting in GOT) *1
host link unit in the C Series.
Set value
0001H
0304H
0000H
(initial status)
00XXH
When RS-232C is used
19200bps
7bit
2bit
Even
Host link mode
Level 1, 2 or 3
1:N procedure
Mode specification: Host link
Communication condition: In accordance with
DM6646
Transmission format: 7 data bits and 2 stop bits
Parity: EvenTransmission speed: 19,200 bps
0 second
xx: Two-digit BCD (in accordance with setting in
GOT)
Introduction 1
Remarks
1-15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

F940got-lwd-e

Table of Contents