Graphic Operation Terminal F940GOT
- Forced setting to ON/OFF in the HPP Mode (GOT function)
In the HPP mode of the GOT, the forced ON/OFF function is available. This function is
available also when the C Series PLC is connected as the host unit.
However, have in mind that the forced ON/OFF function offers the following operation in
the C Series PLC.
* The forced setting/resetting function in the C Series PLC holds the current ON/OFF sta-
tus without regard to a sequence program.
The forced ON/OFF function described here sets a specified bit to ON/OFF. If a
sequence program gives an ON/OFF command after that, the status of the specified bit
device which has been set forcedly to ON/OFF is changed.
Forced ON: Data "1" is specified. (The specified bit is set to ON.)
Forced OFF: Data "0" is specified. (The specified bit is set to OFF.)
• Restriction in functions
When a host link unit is connected, the following GOT functions are disabled or restricted.
- Because the GOT switch function (which sets a bit to ON/OFF) uses a host link com-
mand, FK command (which sets/resets multi points forcedly), the switch function is not
available in models which do not support the FK command.
- The set values of timers (T) and counters (C) cannot be monitored nor changed.
- When the RS-232C is connected, the printer output function of the GOT is disabled.