Mitsubishi F940GOT-SWD-E Operation Manual page 100

Graphic operation terminals melsec-got
Hide thumbs Also See for F940GOT-SWD-E:
Table of Contents

Advertisement

Graphic Operation Terminal F940GOT
2) Reset operation
An occurred alarm (auxiliary relay in the ON status) can be reset to OFF.
Place the cursor in an alarm to be reset using the scroll keys, and press the RESET key 4).
When the alarm device (auxiliary relay) is reset, the corresponding alarm message is
deleted from the list.
However, when the RESET key is set together with the ACK key, the corresponding alarm
message in the list is not deleted even if the alarm device is set to OFF. In such a case, per-
form the confirmation operation described above.
In the sequence program shown below in which an auxiliary relay becomes ON again even
if it is set to OFF once by the reset operation, the alarm device cannot be reset to OFF.
****
ON
M100
M100
* To make the reset operation effective, make sure to set the reset function effective in the
alarm setting in the screen creation software.
3) Detail display (valid when the SW¨D5C-GOTR-PACK is used)
The alarm message list (comment window) or the base screen can be changed over to the
detailed display.
To enable the detailed display, "Detail Display Destination" in "Alarm History Common Set-
ting" in the screen creation software should be set to "Comment Window" or "Base Screen".
• When "Comment Window" is selected
When this button is pressed, the
detailed display window is closed.
DETAIL
*When the FX-PCS-DU/WIN-E is used, comments in the alarm list are displayed.
• When "Base Screen" is selected
The screen of screen No. specified in "Detail Display No." in "Alarm History Common Set-
ting"-"Device Monitor"-"Edit" is displayed.
For example, even if M100 is reset to OFF, M100 will become ON
Alarm has
occurred.
again if the contact **** is ON.
Change the program so that the contact **** which causes the
alarm device M100 to become ON is set to OFF.
• Place the cursor in an alarm message to be displayed to
details, and press the DETAIL key. Then, the detailed dis-
play window is open as shown on the left.
• Comments which are created in "Comment Creation" and
specified by "Comment No." in "Alarm History Common
Setting"-"Device Monitor"-"Edit" are displayed.
Alarm Mode 6
6-8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

F940got-lwd-e

Table of Contents