Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
The following special cases are possible when a keyboard is used for sending of panic alarms:
1. In case of several panics are sent at the same time just the last one will be displayed.
2. When there are 3 keyboards in the system and the configuration is: the 1
nd
1, the 2
keyboard is associated to Area 2, and the 3
case of panics sent the keyboards 1 and 2 will display the panics only in their own areas, and the 3
keyboard will display the both panics. In case the panic is sent from the 3
keyboards will display the panic alarm.
ADDRESS
AREA 1
OPERATION
NAME
TEXT MENU
Programming of the Area 1 Name
The engineer can enter a new name for Area 1 at this address. The name has to be up 16 symbols
– letters (small and capital), digits and special symbols, including spaces.
The letters can be entered directly by the digit buttons. The cursor moves automatically to the right
after choosing of letter or digit, or may be moved manually by the arrows. To enter a digit, press the
respective button and hold it for 2-3 seconds. See also item 2.8. Entering text for LCD Keyboard.
Confirm the new area name with ENTER button.
Default setting: AREA 1
ADDRESS
AREA 1
OPERATION
BDELAY
TEXT MENU
Programming of bell delay for Area 1
The engineer assigns at the address a bell delay for activation of the programmable Siren type
outputs after a burglary alarm event is registered in any arming mode.
The set time delay of this address is considered when the activated zone is not a Fire type and the
option "Bell delay" is enabled in Zone Attributes 2 (at address 2xx5, where "xx" is a zone number).
The bell delay time is set in interval from 000 to 255 seconds.
Default setting: 000 seconds
ADDRESS
AREA 1
OPERATION
TSLOT
TEXT MENU
Programming of time slot for Area 1
An Area 1 timeslot is set.
The valid timeslot numbers are from 1 to 8. If the selected access code is not to be restricted by a
timeslot, enter 0.
Use the digit buttons to enter the timeslot number. The entered number is confirmed with ENTER.
For programming of timeslots, see for details Menu. 5 Timeslot Programming.
Pay attention that when you set time slot number at this address, the Area arming is automatic for
the time slot duration. If at the time slot start time there are open zones in the area the control panel
will wait for zones' restoration (to be ready for arming) and after that will perform automated arming
on the set time slot.
If you program the time slot number at the address and there are less than 10 minutes to its start
time (set at address 5xx0) the area will not be automatically armed at this time. The automatic
arming of the area on the set time slot will perform 24 hours later.
Default setting: 0
The Area numbers from 02 to 03/ 08 are programmed analogically at the respective addresses.
4017
417 + 01
6. PARTITIONS – 5. AREAS – 1. AREA – 08. NAME
4018
418 + 01
6. PARTITIONS – 5. AREAS – 1. AREA – 09. BELL DELAY
4019
419 + 01
6. PARTITIONS – 5. AREAS – 1. AREA – 10. TIMESLOT
rd
keyboard is associated to both Areas 1 and 2, then in
60
st
keyboard is associated to Area
rd
keyboard then the other two
rd