ADDRESS
Z ABYPASS
OPERATION
TEXT MENU
Number of Activations per Zone for Auto Bypass Mode
The number of activations (number of alarm cycles from 1 to 9) in one arm mode, which have to be
accomplished for a zone with an assigned AUTOBYPASS parameter, are entered at this address.
After reaching the set number of activations, the respective zone will be automatically bypassed.
When disarmed and then again armed the respective zone will remain armed.
The 0 value disables the Zone AutoBypass mode even if there is set option "1. AUTOBYPASS" at
address 2хх4, where хх is the zone number.
Default setting: [6]
ADDRESS
OPERATION
Z INSTANT
TEXT MENU
Enabling of Instant type zones
The engineer can enable or disable the intrusion of instant type zones during exit time running at
this address. Enabling this operating mode would reduce the probability for a false alarm signal to be
triggered off by mistake on behalf of the user.
The parameter status can be changed with pressing of random button of the keyboard.
At this address, you set the parameter as:
DISABLE
ENABLE
Default setting: DISABLE
ADDRESS
Z PCOUNT
OPERATION
TEXT MENU
Number of activations in pulse count mode
The number of pulses in Pulse Count mode is assigned at this address.
Values between 1 and 9 pulses can be entered here.
The 0 value blocks the Pulse Count mode and zone can then function with the regular time for
detecting activation.
The working algorithm for zone 4 in Pulse Count mode is described at ADDRESS 2015 – Zone 01
Attributes 2.
Default setting: [0]
ADDRESS
Z TPCOUNT
OPERATION
TEXT MENU
Time for zones in pulse count mode
A time for zones in Pulse Count mode is assigned at this address. Enter a time in interval 0-255 sec.
See also ADDRESS 2015 - Zone 01 Attributes 2 for details.
Default setting: [000]
2001
201
4. INPUTS – 2. AUTO BYPASS
2002
202
4. INPUTS – 3. INSTANT
Disabled intrusion in INSTANT type zones during exit time.
Enables intrusion in INSTANT type zones during exit time.
2003
203
4. INPUTS – 4. PULSE COUNT – 1. PULSES
2004
204
4. INPUTS – 4. PULSE COUNT – 2. TIMEOUT
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
35