Teletek electronics iRIS8 User Operation & Maintenance Manual
Teletek electronics iRIS8 User Operation & Maintenance Manual

Teletek electronics iRIS8 User Operation & Maintenance Manual

Addressable fire alarm control panel
Hide thumbs Also See for iRIS8:

Advertisement

Quick Links

iRIS8
Addressable Fire Alarm Control Panel
User Operation &
Maintenance
Programming
Manual
Attention:
This manual contains information on limitations regarding product use and
function and information on the limitations as to liability of the manufacturer.
The entire manual should be carefully read.
The information in this manual is a subject to change without notice!
ver. 1.0.8

Advertisement

Table of Contents
loading

Summary of Contents for Teletek electronics iRIS8

  • Page 1 Addressable Fire Alarm Control Panel User Operation & Maintenance Programming Manual Attention: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully read.
  • Page 2: Table Of Contents

    - Addressable Fire Alarm Panel – User & Maintenance Manual Table of Contents 1. INTRODUCTION ................................5 1.1. General Description ............................5 1.2. Basic Operation Features ..........................5 1.3. Care of the TFT Screen ..........................5 1.4. Control Access Levels........................... 5 2.
  • Page 3 - Addressable Fire Alarm Panel – User & Maintenance Manual 1293 DoP No: 138 Teletek Electronics JSC Bulgaria, Sofia 1407, 14А Srebarna Str., Tel.: +359 2 9694 800, Fax: +359 2 962 52 13 e-mail: info@teletek-electronics.bg EN 54-2:1997; EN 54-2:1997/AC:1999; EN 54-2:1997/A1:2006 EN 54-4:1997;...
  • Page 4 The manufacturer shall not accept any product, of which no prior notice has been received via the RAN form at: http://teletek-electronics.com/en/ran- form The setup and programming included in the technical documentation shall not be regarded as defects. Teletek Electronics bears no responsibility for the loss of programming information in the device being serviced. CONDITIONS FOR WAIVING THE GUARANTEE This guarantee shall apply to defects in products resulting only from improper materials or workmanship, related to its normal use.
  • Page 5: Introduction

    64 panels, including IRIS/SIMPO Repeater, IRIS PRO and SIMPO fire alarm panels. The connection in the network between the panels can be realised via LAN or RS485 communication protocol.
  • Page 6: Panel Interface

    Note: The front door of iRIS8 addressable fire panel is secured with special key-lock (1 pc in iRIS8 S; 2 pcs in iRIS8 B) for limited access only from technical support specialist. In case you need to replace the text labels, ask your technical...
  • Page 7 - Addressable Fire Alarm Panel – User & Maintenance Manual The different system events are displayed also with color LEDs according their type. In case of fire alarm, common or system faults, settings for delays or disablements, tests or warnings, the LED is lighting on permanently. In case of fault in Fire Output on the main control PCB the respective LED is blinking.
  • Page 8: Led Indication For Activated Zones

    - Addressable Fire Alarm Panel – User & Maintenance Manual 2.2. LED Indication for Activated Zones The LED indication for activated zones is available on the front panel for zone numbers from 1 to 200. The zone number is lighting or blinking according the type of the generated fire alarm together with the status LEDs of the panel.
  • Page 9: Tft Screen

    The icons are changing according the status for Alarm, Fault, Disable or Reset active events. The Alarm indication is with the highest priority. The icons for current status of the iRIS8 or Alarm situation are displayed at the left side of the section and have the following meaning:...
  • Page 10: Section For Events Review

    ** Attention: The iRIS8 indication shows that there are one or more fire panels in the network with disabled for operation output. You can check the DISABLE events menu to review the numbers of these panels.
  • Page 11 WARNINGS Grey In case of incoming Alarm or Fault type messages, the iRIS8 panel will automatically switch on the screen in Events Reviewing Mode and will show the message contents on the right side of the screen. In the expanded screen are shown more details for the 1 –...
  • Page 12 - Addressable Fire Alarm Panel – User & Maintenance Manual The Fault type messages are displayed with high priority. In case the fault is in operation of loop sounders or panel outputs there in also respective indication for that in the status icon section. See examples bellow.
  • Page 13: Main Functional Buttons

    Main Screen to the messages list automatically after 20 seconds. At Access Level 2 and Access Level 3 the iRIS8 panel will switch on to the messages list only in case of new events for Alarm, Fault or Disablement.
  • Page 14: User Operation

    (enabled) to send commands to them. • The iRIS8 panel can receive and display messages for events from other panels in the network only when it is programmed (enabled) to receive commands from them.
  • Page 15: Silencing Buzzer

    The user can silence the buzzer in some exact panels as pressing the button with the respective number. Or, can use the quick buttons: ALL to silence the buzzer in all panels in the network at the same time (including the iRIS8 panel);...
  • Page 16: Access Level 2/3

    - Addressable Fire Alarm Panel – User & Maintenance Manual 3.2. Access Level 2/3 At Access Level 2/3 the users can perform: - Review events for the panel and the network – see the details in item 2.3.2. - Silence Buzzer of the panel or other fire panels in the network – see the details in item 3.2.1.
  • Page 17: Resetting Panel

    In case of receiving of fire alarm event, iRIS8 will turn on automatically to the alarm events list, showing information for the fire alarm. In that case the User can return to Main Screen pressing the MENU or EXIT button and to initiate immediate Evacuation to this and/or other panels in the system.
  • Page 18: Changing The Access Level

    3.4.2. Auto Log Out According the programmed parameters of iRIS8 fire alarm panel, it is possible automatic logging out from the current set Access Level 2 or 3 after a time period and no operation with the panel. The time period for automation log out is...
  • Page 19: Screen Saver" - Company Information

    Installer’s Access Level 3 only. If the automatic log out is enabled, the panel will log out to Access Level 1 when the programmed time is over. Note: Ask your Installer or Support Engineer if Auto Log Out option is programmed for the used iRIS8 fire alarm panel. 3.5. “Screen saver” – Company Information This is an option for turning off the Main Screen and displaying some company information while the panel is in normal operation mode.
  • Page 20: Programming Menus

    - Addressable Fire Alarm Panel – User & Maintenance Manual 4.1. Programming Menus In Programming menus, at Access Level 2 the user can perform limited actions for zones and loop devices available for operation with the panel. Enter PROGRAMMING menu. The available for operation submenus are performed with active buttons in blue.
  • Page 21: Zones - Quick Review

    - Addressable Fire Alarm Panel – User & Maintenance Manual 4.1.2. Zones – Quick Review Next to ZONES menu is situated button << GRID VIEW for quick reviewing the operation status of all zones. The zones are reviewed at several screens, as 60 numbers are displayed at the same time.
  • Page 22 - Addressable Fire Alarm Panel – User & Maintenance Manual To change the device operation status (2), press the active button next to system name field. Every pressing of the button changes the current status Enabled/Disabled. The device is Enabled for operation. To disable it, press The status is changed to Disabled and must be confirmed the button.
  • Page 23: Loop Devices - Quick Review

    - Addressable Fire Alarm Panel – User & Maintenance Manual 4.1.4. Loop Devices – Quick Review Next to LOOP menu is situated button << GRID VIEW for quick reviewing the operation status of all loop devices. The devices are reviewed at several screens, as 50 address numbers are displayed at the same time. The devices can be reviewed also loop by loop.
  • Page 24: Setting Time

    - Addressable Fire Alarm Panel – User & Maintenance Manual 4.2.1. Setting Time Enter MAINTENANCE - TIME menu. Use the up and down arrow buttons to set the time. Confirm the new set time with APPLY button. You can also directly enter the new settings using the The panel will change the time immediately without need keyboard after selecting the digit button for hour/minutes.
  • Page 25: Review The Log Memory For Events

    - Addressable Fire Alarm Panel – User & Maintenance Manual The introduced settings for time delay for activation of the panel’s outputs must be confirmed with Apply button. Press Apply button to confirm the set configuration. In the The time schedule table presents the preprogrammed...
  • Page 26: Clear The Log Memory For Events

    - Addressable Fire Alarm Panel – User & Maintenance Manual 4.2.5. Clear the Log Memory for Events This is a submenu in View Log for deleting the contents of the log memory file. Enter MAINTENANCE - VIEW LOG submenu.
  • Page 27 - Addressable Fire Alarm Panel – User & Maintenance Manual Single long sound from the panel’s buzzer will inform for Selected zone numbers are presented with black digit on dark grey button. Next pressing of selected zone number stating zone tests. At events list are registered messages deselects it.
  • Page 28: Performing Disablements

    This is a menu for testing the operability of the monitored sounder outputs on the control panel’s PCB. Note: The Sounder Output Test will be applied to all SND outputs of the used iRIS8 fire alarm panel. The number of the SND outputs depends on the model and configuration: - Single panel iRIS8 S (up to 4 loops) –...
  • Page 29 - Addressable Fire Alarm Panel – User & Maintenance Manual 4.2.7.3. Zones Devices Press the ZONE DEVICES button. This is a special grid view menu presenting the attached devices to zone and loop number. The devices are reviewed at several screens, as 50 address numbers are displayed at the same time. The user sets the loop and zone number to review the attached devices.
  • Page 30 - Addressable Fire Alarm Panel – User & Maintenance Manual APPENDIX А Table: Event Messages. Note: The messages are followed from a Panel, Zone and Loop number, and also Device address, when the event is received from another panel in the network.
  • Page 31 - Addressable Fire Alarm Panel – User & Maintenance Manual Earth Fault function DISABLED The Earth Fault indication is disabled. Sounder Disabled The Sounders are disabled. Fire Brigade Output Disabled The fire output is disabled. Fire Protection Output Disabled The extinguishing output is disabled.
  • Page 32 - Addressable Fire Alarm Panel – User & Maintenance Manual APPENDIX B Table: SensoIRIS series – names and description of supported devices. Device System Name Description Isolator Module Available SensoIRIS S130 Optical-smoke detector SensoIRIS S130 IS Optical-smoke detector Yes (built-in)
  • Page 33 - Addressable Fire Alarm Panel – User & Maintenance Manual APPENDIX C Menu Structures: Access Level 1 and Access Level 2.
  • Page 34: Routine Maintenance

    Routine Maintenance iRIS8 S and iRIS8 B control panels do not require any specific maintenance. To clean the panel’s surface, use a dry cloth. Detergents or solvents should not be used to clean the panel and care must be taken that water does not enter the enclosure.
  • Page 35 - Addressable Fire Alarm Panel – User & Maintenance Manual Notes:...
  • Page 36 www.teletek-electronics.com Address: Bulgaria, 1407 Sofia, 14А Srebarna Str. Tel.: +359 2 9694 800, Fax: +359 2 962 52 13 e-mail: info@teletek-electronics.bg English, RevA, 10/ 2021...