Default setting:
ADDRESS
AREA 1
OPERATION
PANICS
TEXT MENU
Setting of Panic types for Area 1
The setting for panic events concerns only the alarm signals sent via the keyboard quick panic
buttons. The keyboard must be associated to Area 1 for sending the panic alarm messages. The
quick button combinations for panics are: 1+3 for police alarm, 4+6 for medical alarm, and 7+9 for
fire alarm. To send an alarm signal just press and hold together the button combination for at least
2-3 seconds.
Two types of panic alarm can be set:
Silent panic (panics 2. Silent police and 4. Silent medical are set at this address) – only the
programmable Panic types outputs and the digital communicator are activated. There is no
indication for memory event. After entering of valid user code, the MEMORY LED lights on together
with the number of the activated zone.
Audible panic (panics "1. Police", "3. Medical" and "5. Fire alarm" are set at this address) – the
programmable Siren and Panic outputs and the digital communicator are activated. The sirens are
activated immediately with no time delay.
More than one panic can be assigned at this address.
At this address for you set the following attributes:
1
Panic Police
2
Panic Police
Silent
3
Panic Medical
4
Panic Medical
Silent
5
Fire Panic
To select all panic alarms press button "0" – the button alternatively switches over all enabled / all
disabled state.
Default setting: All disabled
5 – The automatic arming on no movement in the zones is enabled.
Area 1 will be automatically armed after ending the time set at
ADDRESS 4002 when there is no movement in the zones associated to
the Area 1.
4. Quick ARM
4016
416 + 01
6. PARTITIONS – 5. AREAS – 1. AREA – 07. PANICS
Audible Panic police alarm:
– Not used. The panic is disabled.
1 – The audible panic is enabled. The user can send Panic police alarm
message with pressing and holding the buttons 1+3 for 2-3 seconds.
Silent Panic police alarm:
– Not used. The panic is disabled.
2 – The silent panic is enabled. The user can send Panic police alarm
message with pressing and holding the buttons 1+3 for 2-3 seconds.
Audible Panic medical alarm:
– Not used. The panic is disabled.
3 – The audible panic is enabled. The user can send Panic medical alarm
message with pressing and holding the buttons 4+6 for 2-3 seconds.
Silent Panic medical alarm:
– Not used. The panic is disabled.
4 – The silent panic is enabled. The user can send Panic medical alarm
message with pressing and holding the buttons 4+6 for 2-3 seconds.
Audible Panic fire alarm:
– Not used. The panic is disabled.
5 – The audible panic is enabled. The user can send Panic fire alarm
message with pressing and holding the buttons 7+9 for 2-3 seconds.
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
59