appropriate for connecting of control or signal devices. The keyboard PGM takes all common setting
for PGM outputs. To add a keyboard PGM output to the system configuration it must be first
attached to a PGM address and device – the device in this case is the keyboard ID number.
According to the system configuration the keyboard PGM can be attached to any free PGM number
at address 3xx0, where xx is a PGM number from 06 to 32.
Example 1. At address 8020 (Device 02) to the control panel is enrolled a keyboard with one on
board PGM output. Choose a free PGM address in the system configuration, number 15 for
example, where to attach the keyboard PGM. Enter in the engineer programming menu, type
address 3150, enter in sequence number of device 02, and output number 01. The screen displays:
Example 2. At address 8100 (Device 10) to the control panel is enrolled a PGM expander with 8 on
board PGM outputs. Choose a free PGM output in the system configuration, number 20 for example,
where to attach the first output of the expander. Enter in the engineer programming menu, type
address 3200, enter in sequence number of device 10, and output number 01. The screen displays:
To use the second PGM output of the same expander you have to attach it to other free PGM
address in the system configuration – for example 21. Then at address 2210 you should enter in
sequence number of device 10 and output number 02. In analogical way, proceed with the other
PGM outputs of the expander to attach them to free PGM addresses in the system configuration.
The attached PGM outputs cannot be programmed for operation as a fire zone like PGM4.
ADDRESS
PGM 01
OPERATION
OPTION
TEXT MENU
Programming of PGM 01 Options
The engineer sets a number of options for operation of the PGM 01 at this address. More than one
option is available to set. To select the option press the digit button corresponding to its number.
The selected options are confirmed with ENTER button.
Pay attention that both of the option statuses are used – see the description of the options in the
table below. The option numbers 3, 4 and 5 are available only for ECLIPSE 32 control panel.
The following Options are available for setting at this address:
No
Option
1
GENERAL
OUTPUT/
SIREN
2
POLARITY
NORMAL/
INVERT
3150>P15 ATTACH
3200>P20 ATTACH
3011
311 + 01
5. OUTPUTS – 2. PGMs – 01. PGM – 2. OPTIONS
Description
The option concerns the operation of PGM 01 as output:
GENERAL OUTPUT
SIREN (1) – PGM1 operates as siren output. With setting this option, the
PGM 01 takes all common settings for sirens in the system and the
settings for activation and deactivation events at addresses 3013 - 3018
are not used. The output is activated, when there is an alarm event in
zones associated to areas assigned to PGM 01 at ADDRESS 3012.
The option concerns the active state of PGM 01:
NORMAL ()
(NO) The active state of the output is at high level: +12 V
INVERT (2)
(NC) The active state of the output is at low level: 0 V
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
[02] [01]
[10] [01]
– PGM1 operates as general output.
()
47