Default setting:
ADDRESS
AREA 1
OPERATION
ATTR 2
TEXT MENU
Programming of ON/OFF attributes for Area 1
The ON/OFF (ARM/ DISARM) attributes for Area 1 are programmed at this address. Every attribute
is activated with pressing of a digit button with a respective number (from 1 to 5).
Next pressing of the same button number will deactivate the attribute. At end of the procedure, at
the keyboard's display must be active only the numbers of the assigned attributes.
More than one attribute can be assigned at this address.
Pay attention that both of the attribute statuses are used – see their description in the table below.
The attribute numbers 1, 2 and 5 are available only for ECLIPSE 32 control panel.
At this address you set the following attributes:
1
2
3
4
5
Squawk on
Sound signalization in disarming:
– The sound signalization in disarming is disabled.
Disarm
2 - The sound signalization in disarming is enabled. The siren will
activate twice for 1 second when disarming the Area 1.
Ring Back
Sound signalization for memory log record:
– The sound signalization for memory log record is disabled.
Squawk
3 - The sound signalization for memory log record is enabled. The siren
will activate 4 times for 1 second in disarming the Area 1 if there was an
alarm event in the Area.
10 minutes
10 minutes warning signal before automatic arming on time slot:
– The 10 minutes warning signal is disabled.
Warning
4 – The 10 minutes warning signal is enabled. The siren will activate 3
times for 1 second 10 minutes before the start of automatic arming on
time slot.
Fire Alarm
FIRE Alarm duration. This attribute is applicable for Fire type zones or
sending of Fire alarm via keyboard button's combination.
Duration
Programming this attribute affects the performance of the programmable
SIREN output.
- Until the Bell time at address 4012 ends.
5 - Until a valid user or manager code is entered.
5. Fire Alarm Duration
4015
415 + 01
6. PARTITIONS – 5. AREAS – 1. AREA – 06. ON/OFF OPTIONS
Auto disarming
Automatic disarming on time slot:
– Not used.
on Time Slot
1 – The Area 1 is disarmed according the set time slot number at
ADDRESS 4019.
Auto ARM type –
Setting the arming type on time slot:
– Full Arming mode. The type of automatic arming is Full ARM.
Full, Stay
2 – Stay Arming mode. The type of automatic arming is Stay ARM.
Clear Bypass on
Clear the bypassed zones on disarm:
– The bypassed zones are not cleared on disarm.
Disarm
3 – The bypassed zones are cleared on disarm.
Quick ARM
Quick arming with one button:
– Not used. The user has to enter valid code for arming.
4 – The quick arming is enabled. To arm an area the user has to hold
the arming button for 2-3 seconds.
Auto ARM on no
Automatic arming when there is no movement in the zones associated to
movement
Area 1:
– Not used.
58