Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
No
1
2
3
4
5
6
7
8
Default setting: 2. BYPASS
ADDRESS
Z1 ATTR 2
OPERATION
TEXT MENU
Setting of Additional Attributes for Zone 01
According the system configuration the engineer sets a range of additional attributes for ZONE 01.
More than one attribute can be assign to the zone. To select an attribute press the digit button
corresponding to its number. The next pressing of the same button will deselect the attribute.
To select all attributes press button "0" – the button alternatively switches over all enabled / all
disabled state.
Some of the Attributes are not available in ECLIPSE 8/ 16 control panel.
The following Attributes are available for setting at this address:
No Attribute
1
Attribute
Authorization for automatic Bypassing the zone after reaching the number
Auto BYPASS
of activations per armed mode as set at address 2001 (OPERATION 201)
for an arming mode.
Authorization to Bypass a zone. Assigning this attribute to the respective
BYPASS
zone will authorize bypass of the zone on behalf of the system user or
manager.
The zone is not going to be armed in the STAY mode. Assigning this
Stay ARM
attribute will authorize bypassing of the zone during Stay arming mode.
The zone is not going to be armed in the SLEEP mode. Assigning this
Sleep ARM
attribute will authorize bypassing of the zone during SLEEP arming mode.
If when arming the system the zone is open (activated), then the
respective
Force ARM
AREA will be armed, and the respective zone will be armed after its
restoration.
DOUBLE KNOCK type zone. Assigning this attribute to the respective
zone authorizes Double Knock mode performance in the zone.
A 1 to 5-minute time interval (set at ADDRESS 4001) starts when a
DOUBLE
detector in the zone is activated for the first time when the system is
KNOCK
armed. An alarm event is registered if second detector activation is
recorded within this interval in the same or another zone.
An alarm event will also be registered if no zone is restored within 15 sec.
of the first activation of the zone.
When armed the zone will perform as Entry/Exit type.
The system will be armed:
E/E FINAL
А) When the exit time is over;
B) 3 seconds after closing the entry-exit zone.
Programmable sensitivity of the zone – choose between 64ms (fast) and
256ms (regular).
FAST/
Indication:
REGULAR
LCD: REGULAR –  / FAST – 8
LED: REGULAR – / FAST –
2015
215 + 01
4. INPUTS – 5. ZONES – 01. ZONE – 5. OPTIONS
The siren will be activated when the set Bell Delay time is over. The Bell Delay
time can be programmed at ADDRESS 4xx8 (for Partition A), where xx is the
Bell Delay
area number.