Teletek electronics ECLIPSE 8 Installation Manual
Teletek electronics ECLIPSE 8 Installation Manual

Teletek electronics ECLIPSE 8 Installation Manual

Alarm control panel
Hide thumbs Also See for ECLIPSE 8:

Advertisement

INSTALLATION
MANUAL
ECLIPSE 8
(S.W. 1.87)
ECLIPSE 32
(S.W. 1.87)
ALARM CONTROL PANELS
Attention:
This manual contains information on limitations regarding product use and
function and information on the limitations as to liability of the manufacturer.
The entire manual should be carefully read.
The information in this manual is a subject to change without notice!

Advertisement

Table of Contents
loading

Summary of Contents for Teletek electronics ECLIPSE 8

  • Page 1 INSTALLATION MANUAL ECLIPSE 8 (S.W. 1.87) ECLIPSE 32 (S.W. 1.87) ALARM CONTROL PANELS Attention: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully read.
  • Page 2: Table Of Contents

    Eclipse 8/ 32 Series - Installation Manual Table of Contents: QUICK STEPS OF INSTALLATION ..........................4 1. GENERAL INFORMATION ............................6 2. INSTALLATION ................................7 2.1. Control Panels Mounting ..........................7 2.1.1 ECLIPSE 8 ............................7 2.1.2 ECLIPSE 32 ............................. 8 2.2.
  • Page 3 The manufacturer shall not accept any product, of which no prior notice has been received via the RAN form at: http://www.teletek- electronics.com/en/support/Service The setup and programming included in the technical documentation shall not be regarded as defects. Teletek Electronics bears no responsibility for the loss of programming information in the device being serviced. CONDITIONS FOR WAIVING THE GUARANTEE This guarantee shall apply to defects in products resulting only from improper materials or workmanship, related to its normal use.
  • Page 4: Quick Steps Of Installation

    Connect the detectors in the zones as use one of the following connection diagrams according the respective application. According your system you can choose among different connection styles diagrams: ECLIPSE 8 – 5 connection styles diagrams for single zone connection ECLIPSE 32 – 9 connection diagram styles for single and doubling zone connection Use the detailed connection diagrams provided in item 2.3 of this manual.
  • Page 5 3. Program the parameters of the PGM outputs, time slots, areas and users in the system – for details see the Programming tables in the ECLIPSE 8/ 32 Series - Engineer Programming Manual. Note: If the PGM5 output is not used for connecting siren you must program it as PGM with general application – at address 3051, option 1 is off.
  • Page 6: General Information

     Avoid any loops of connecting wires within the very box and in their passage over or under the printed circuit boarding.  Additional relays MUST NOT be placed in the Eclipse 8/32 Alarm control panel box as these may generate electromagnetic interference when switched.
  • Page 7: Installation

    2.1.1 ECLIPSE 8 ECLIPSE 8 Alarm Control Panel is mounted in a white plastic box with dimensions 290 x 240 x 80mm. There is additional space for mounting of one communication module in the box. For the back-up battery is provided special place.
  • Page 8: Eclipse 32

    Eclipse 8/ 32 Series - Installation Manual 2.1.2 ECLIPSE 32 ECLIPSE 32 Alarm Control Panel is mounted in a white plastic box with dimensions 335 x 290 x 105mm. There are additional spaces for mounting of one communication module in the box and one expander module (under the main PCB).
  • Page 9: Control Panels Pcb Layouts

    Eclipse 8/ 32 Series - Installation Manual 2.2. Control Panels PCB Layouts 2.2.1 ECLIPSE 8 Figure 5. ECLIPSE 8 control panel ECLIPSE 8 - Terminals and components: 17VAC – Power supply from a mains transformer 17V / 17VA, fuse 0.63А...
  • Page 10: Eclipse 32

    Eclipse 8/ 32 Series - Installation Manual 2.2.2 ECLIPSE 32 Figure 6. ECLIPSE 32 control panel ECLIPSE 32 - Terminals and components: 17VAC – Power supply from a mains transformer 15-25V / 50VA, fuse 0.63А GND – Common ground +/- AUX – Power supply for detectors with consumption up to 0.75А...
  • Page 11: Zone Connection

    ADDRESS 2000 (OPERATION 200) and it is common for all zones in the system. ATTENTION: ECLIPSE 8 Control panel supports only single connection in the zones. ECLIPSE 32 Control panel supports both single and doubling connection in the zones.
  • Page 12: Examples For Detector Connection

    Eclipse 8/ 32 Series - Installation Manual Examples for realizing different connection styles using TITAN series detectors. NOTE: The connection style 3. NO with EOL is applicable only for detectors with normal open (NO) type terminals. 4. NC without EOL, TAMPER 1.
  • Page 13: Connecting Shutter Detector To A Zone (For Eclipse 32)

    Eclipse 8/ 32 Series - Installation Manual 2.3.2 Connecting shutter detector to a zone (for ECLIPSE 32) The hardware implementation of Zone with set attribute “Pulse count” permits performance in pulse count mode, suitable for connecting a rolling shutters detector. This mode counts short pulses - 2 to 4 ms for a period of 20 seconds.
  • Page 14: Connecting Fire Lines

    2.3.4 Connecting Fire Lines Fire detectors can be connected to every zone set as Fire type zone. For ECLIPSE 8 are possible to realize only 4-wire connections of 12V alarm fire base with one or two balancing resistors. For ECLIPSE 32 are possible to realize 4-wire connections of 12V alarm fire base with one or two balancing resistors and also connection of two fire detectors to a doubling zone.
  • Page 15: Connection Of Peripheral Devices

    Eclipse 8/ 32 Series - Installation Manual 2.4. Connection of Peripheral Devices 2.4.1 Connection to the System Bus ECLIPSE Control Panels Series – DEVICE capability: Control panel Max. supported devices Keyboards Proximity card readers Exp. modules    ECLIPSE 8 ...
  • Page 16: Supported Keyboards

    Eclipse 8/ 32 Series - Installation Manual 2.4.2 Supported Keyboards Summary for ECLIPSE Series Keyboards: Keyboard Display Areas Zones Proximity card reader 1 x AUX PGM   LED 8   LED 16  (option)  LED 32 ...
  • Page 17 Eclipse 8/ 32 Series - Installation Manual  Technical Specifications: Feature LED 8 LED 16 LED 32 LCD 32 LCD 32 Sens. Power Supply 9-18V (nom. 14V) Min. 50mA / Min. 50mA / Min. 60mA / Min. 60mA / Min. 50mA / Consumption Max.
  • Page 18: Supported Expander Modules

    Eclipse 8/ 32 Series - Installation Manual Bypassing zones. The button lights on permanently if there are bypassed zones in the system. The button is blinking during the bypassed zones review. BYPASS The button has a special function in engineer programming – canceling the entered settings and moves forward as the current index number is increased with +1, option 0.
  • Page 19 Eclipse 8/ 32 Series - Installation Manual  Expanders’ Terminals and Specifications Button Button +PGM – Power supply for auxiliary devices with consumption up to 0.75А +/- AUX – Power supply for detectors with consumption PGM 1-8 – Programmable outputs, 100mA, ОС type (open up to 0.75А...
  • Page 20: Supported Proximity Card Readers

    Trouble indications. Portable LED or LCD type keyboards can be used to accomplish such tasks. Up to 8/64 cards can be assigned to one ECLIPSE 8/ 32 security systems - one card for each of the 8/ 64 users. The Managers in the system are allowed to program the performance of the cards.
  • Page 21: Connection Of Pgm Outputs

    In ECLIPSE 8, when set at address 3000, PGM 4 can be used for serial connection to TP2000 transmitter. The serial link is realized with connection between the AC terminal of the transmitter and PGM 4 on the ECLIPSE 8 – Figure 18.
  • Page 22: Connection Of Siren To Pgm5 Output

    2.6. Connection of Siren to PGM5 Output In ECLIPSE 8 Alarm panel the PGM 5 (SIREN) output has a programmable active level. The default configuration of PGM5 is with SIREN functionality. The output is activated in case of alarm event in the system. The output is non- monitored.
  • Page 23: Connecting The Digital Communicator

    2.7. Connecting the Digital Communicator The telephone line is connected to A and B terminals on the ECLIPSE 8/ 32 Control Panel with no requirements to observe polarity (see Figure 5 for ECLIPSE 8 panel and Figure 6 for ECLIPSE 32 panel). The telephone device is connected to A1 and B1 terminals on the ECLIPSE 8/ 32 Control Panel with no requirements to observe polarity.
  • Page 24: Connecting Communication Modules

    Eclipse 8/ 32 control panel. Connect the PSTN main line to the LINE connector of ARGUS module. Connect the PHONE connector of ARGUS module to the RING and TIP terminals of Eclipse 8/ 32. Connect a telephone to RING1 and TIP1 terminals.
  • Page 25: Trouble Events

    IMPORTANT NOTE! When enrolling devices to ECLIPSE 8 control panel, the first is automatically added to ZONE 7, and the second to ZONE 8! 5.2. Enrolling Devices to a working system configuration via LCD keyboard 1.
  • Page 26: Enrolling Devices To A Working System Configuration Via Led Keyboard

    LED8 Keyboard LED 8 * Eclipse 8: Up to 2 devices can be enrolled to the system bus: 2 keyboards, 2 proximity card readers or 1 keyboard and 1 proximity card reader. ** Eclipse 32: Up to 31 devices can be enrolled to the system bus irrespective of their type.
  • Page 27: Deleting Of A Device From The System Configuration

    Eclipse 8/ 32 Series - Installation Manual 5. Press ENTER button of the used for programming keyboard. The keyboard will confirm the end of the successful enrollment procedure with sound signal. 6. The new enrolled device is in normal operation mode and ready for further programming and configuration.
  • Page 28 www.teletek-electronics.com Address: Bulgaria, Sofia - 1407, 14А Srebarna Str. Tel.: +359 2 9694 800, Fax: +359 2 962 52 13 e-mail: info@teletek-electronics.bg 18020130, Rev B, 10/ 2013...

This manual is also suitable for:

Eclipse 32Eclipse 16

Table of Contents