Teletek electronics ECLIPSE 16 Engineer Programming Manual page 51

Alarm control panels
Table of Contents

Advertisement

Alarm cycle
Activated on "OR" function (if at least one of
12
the set zone numbers is in alarm the PGM
ZONE IN
is activated)
Deactivated on "AND" function (when all of
ALARM
the set zone numbers are alarm restored
the PGM is restored too)
13
Not used
Zone in Fire Alarm
Activated on "OR" function (if at least one of
14
the set area numbers is in fire alarm the
ZONE IN
PGM is activated)
Deactivated on "AND" function (when all of
FIRE
the set area numbers are fire alarm
restored the PGM is restored too)
15
Not used
Zone in Medical Alarm
Activated on "OR" function (if at least one of
16
the set area numbers is in medical alarm
the PGM is activated)
ZONE IN
Deactivated on "AND" function (when all of
MEDICAL
the set area numbers are medical alarm
restored the PGM is restored too)
17-19
Not used
Event No
AREA Event - Description
Area Arming
Activated on "OR" function (if at least one of
all area numbers is armed the PGM is
20
activated)
AREA ARM
Deactivated on "AND" function (when all
area numbers are disarmed the PGM is
restored)
Area Disarming
Activated on "AND" function (when all area
numbers are disarmed the PGM is
21*
activated)
Deactivated on "OR" function (if at least one
area number is armed the PGM is restored)
22-26
Not used
Alarm in Area
Activated on "OR" function (if at least one
27
area number is in alarm the PGM is
ALARM IN
activated)
Deactivated on "AND" function (when all
AREA
area numbers are alarm restored the PGM
is restored too)
Alarm in Area – Restore
Activated on "AND" function (when all area
numbers are alarm restored the PGM is
28*
activated )
Deactivated on "OR" function (if at least one
area number is in alarm the PGM is
restored)
Panic Alarm in Area
Activated on "OR" function (if at least one
29
area number is in panic alarm the PGM is
PANIC IN
activated)
Deactivated on "AND" function (when all
AREA
area numbers are panic alarm restored the
PGM is restored too)
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
Enter zone number "FROM"
Enter zone number "FROM"
Enter zone number "FROM"
-
PARAMETERS 1
Enter the arming type:
1 – FULL arming
2 – STAY arming
3 – SLEEP arming
All arming types are enabled
by default.
-
-
Enter the alarm type:
1 – Burglary alarm
2 – Fire alarm
3 – Panic alarm
4 – Tamper alarm
5 – Medical alarm
6 – Ambush code
All alarm types are enabled
by default.
Enter the alarm type:
1 – Burglary alarm
2 – Fire alarm
3 – Panic alarm
4 – Tamper alarm
5 – Medical alarm
6 – Ambush code
All alarm types are enabled
by default.
Enter the panic type:
1 – Silent panic
2 – Sound panic
3 – Silent medical
4 – Sound medical
5 – Fire
51
Enter zone number "TO"
"00" – not used, operates only
"FROM"
Enter zone number "TO"
"00" – not used, operates only
"FROM"
Enter zone number "TO"
"00" – not used, operates only
"FROM"
-
PARAMETERS 2
-
-
-
-
-
-