Teletek electronics ECLIPSE 16 Engineer Programming Manual page 37

Alarm control panels
Table of Contents

Advertisement

Example 1. At address 8020 (Device 02) to the control panel is enrolled a keyboard with one on
board zone input. Choose a free zone in the system configuration, number 15 for example, where to
attach the keyboard zone. Enter in the engineer programming menu, type address 2150, enter in
sequence number of device 02, and input number 01. The screen displays:
Example 2. At address 8100 (Device 10) to the control panel is enrolled a zone expander with 8 on
board zone inputs. Choose a free zone in the system configuration, number 20 for example, where
to attach the first zone of the expander. Enter in the engineer programming menu, type address
2200, enter in sequence number of device 10, and input number 01. The screen displays:
To use the second zone input of the same expander you have to attach it to the next free zone in the
system configuration – for example 21. Then at address 2210, you should enter in sequence
number of device 10 and input number 02. In analogical way proceed with the other zone inputs of
the expander to attach them to free zones in the system configuration.
ADDRESS
Z1 TYPE
OPERATION
TEXT MENU
The type of ZONE 01 is set at this address.
Only one type can be selected for a zone!
Press the digital button, which corresponds to the number of the desired type.
No
Type
0
UNUSED
1
ENTRY/ EXIT
2
FOLLOW
2150>Z15 ATTACH
2200>Z20 ATTACH
2011
211 + 01
4. INPUTS – 5.ZONES – 01. ZONE – 2. TYPE
The zone is not used.
Entry- Exit zone.
Provides time to arm and disarm the site. After arming, the detector,
which was triggered off in this zone, will not sound an alarm until the
programmed EXIT TIME expires for the Area (or Areas) to which the
zone is attached.
No violation of the zone when in armed mode will sound an alarm before
the programmed ENTRY TIME expires for the Area (or Areas) to which
the zone is attached.
A sound signal is activated from the keyboard buzzer during entry and
exit time.
In SLEEP ARMING mode, the entry-exit type zones become instant and
no entry or exit time starts running when violation in the zone accures –
the programmable ALARM and SIREN type outputs, and the
communicator are activated at once.
Follow zone.
An alarm zone which is active only when the site is armed in Full and
Stay arming. The zone operates instantaneously and activates the
programmable ALARM and SIREN type outputs, and the communicator.
Activating the zone during entry or exit time does not cause an alarm
event.
The entry time will start running if the follow type zone is activated while
the system is in SLEEP ARMING mode.
When the system is disarmed, the activation of a zone is indicated by
blinking of the respective light-emitting diode for the zone (LED
keyboards) or displayed zone name and number (LCD
keyboards) for the time that the zone remains open (The
displayed mode can be disabled for Eclipse 32 control panel at the
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
[02] [01]
[10] [01]
Description
37