Notifier NFS-640 Operation Manual
Notifier NFS-640 Operation Manual

Notifier NFS-640 Operation Manual

Fire alarm control panel
Hide thumbs Also See for NFS-640:
Table of Contents

Advertisement

Quick Links

Fire Alarm Control Panel
NFS-640
Operations Manual
Document 51334
B
10/03/2003
Rev:
P/N 51334:B
ECN 03-419
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NFS-640 and is the answer not in the manual?

Questions and answers

Summary of Contents for Notifier NFS-640

  • Page 1 Fire Alarm Control Panel NFS-640 Operations Manual Document 51334 10/03/2003 Rev: P/N 51334:B ECN 03-419 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 2 (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.). Precau-L-4-2003.fm NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 3 Acclimate Plus™, AWACS™, HARSH™, NOTI•FIRE•NET™, ONYX™, and VeriFire™ are trademarks, and FlashScan®, UniNet®, and VIEW® are registered trademarks of NOTIFIER. NION™ is a trademark of NIS. NIS™ and Notifier Integrated Systems™ are trademarks and NOTIFIER® is a registered trademark of Fire•Lite Alarms, Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation.
  • Page 4 Your suggestion for how to correct/improve documentation Send email messages to: TechPubs@fla-whq.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 5: Table Of Contents

    Disabled Points Mode of Operation ................. 32 Non-Alarm Mode of Operation ................33 Purpose of Non-Alarm Points ................. 33 How the Control Panel Indicates an Active Fire Control ........33 NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 6 Appendix A: Special Zone Operation Overview........................55 Releasing Zones (R0-R9)................... 56 Purpose of Releasing Zones ................. 56 How to View Releasing Zone Selections..............56 How Releasing Zones Operate................57 NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 7 Clear the Entire History Buffer ................77 Set the Pre-Alarm for Alert or Action..............78 Appendix D: Point and System Troubles Lists Point (Device) Troubles..................... 79 System Troubles......................80 NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 8 Notes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 9: About This Manual

    In a graphic, a key as it Press means to press the Escape key appears on the control panel Table 1 Typographic Conventions in this Manual NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 10: Supplemental Information

    Compatible Conventional Devices (Non-addressable) Document Number Device Compatibility Document 15378 Fire Alarm Control Panel (FACP) and Main Power Supply Installation Document Number NFS-640 Installation, Operations, and Programming Manuals 51332, 51334, 51333 Voice Alarm System Manual 51252 SLC Wiring Manual 51253...
  • Page 11: Shortcuts To Operating Functions

    For example, the keypad shortcut to the left, shows how to enter the Read Status function with the control panel in normal operation, as well as how to exit the function. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com...
  • Page 12 Notes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 13: Introduction

    1. Introduction Product Description The NFS-640 is a modular, intelligent Fire Alarm Control Panel (FACP) with an extensive list of powerful features suitable for most applications. Operating Features • Alarm Verification selection, to reduce unwanted alarms, for intelligent detector points •...
  • Page 14 Notes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 15: Use Of The Controls

    SELECTION RECALL & OUTPUT LAST ENTRY Enter SPACE BATTERY INCREMENT LEVELS NUMBER Programming Keypad Cursor movement (arrow) keys, key, and ENTER Figure 1 Control Panel Keys and Indicators NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 16: System Status Indicator Leds

    Lights when one or more system devices Enable the device or remove the POINT are disabled. disabled device from the system DISABLED program. Table 3 Descriptions of System Status Indicator LEDs NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 17: Control Keys

    Sends a Manual Evacuate message to the History buffer and installed printers, CRT-2 terminals, and terminal mode LCD-80s Note: If Local Control is set to “NO”, the FACP will not respond to DRILL. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 18: System Reset

    Lights all segments of the LCD display. When the key is held for longer than five LAMP TEST seconds, the LCD will display the Software Revisions. • Lights all panel circuit LEDs NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 19: Programming Keypad

    – press to exit a selection or move the cursor one place to the left Figure 4 Programming Keypad NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 20 Notes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 21: Operation Of The Control Panel

    NFPA 12. Do not enter the protected space unless physical lockout and other safety procedures are fully completed. Do not use software disable functions in the panel as lockout. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com...
  • Page 22: Normal Mode Of Operation

    Refreshes the LCD display and the optional terminal mode LCD-80 display and updates time • Scans for any keypad or Control Key entries • Performs a detector automatic test operation • Tests system memory • Monitors for microcontroller failure NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 23: Fire Alarm Mode Of Operation

    (indicated by the “System Normal” message). The control panel sends a “System Normal” message to the LCD display, History buffer and installed printers, terminal mode LCD-80s, and CRT-2s. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 24: Interpreting Fire Alarm Type Codes

    LED and activates CBE FIRE ALARM freeze warning LED and activates CBE SMOKE MULTI* Multisensor smoke detector Lights FIRE ALARM *CLIP mode only Table 4 Fire Alarm Type Codes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 25: System Trouble Mode Of Operation

    Correct the condition causing the trouble. If the trouble clears, the control panel sends a Clear Trouble message to the History buffer and installed printers, terminal mode LCD-80s, and CRT-2s. Continued on the next page... NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 26 ACKNOWLEDGE SCROLL DISPLAY Refer to Appendix D: Point and System Troubles Lists on page 79 for explanations of troubles that appear on the display. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 27: Security Alarm Mode Of Operation

    (indicated by the “System Normal” message). The control panel sends a “System Normal” message to the LCD display, History buffer and installed printers, terminal mode LCD-80s, and CRT-2s. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 28: Interpreting Security Type Codes

    SECURITY Monitors security switches for tampering Lights SECURITY LED, activates CBE SYS MONITOR Monitors critical equipment for security Lights SECURITY LED, activates CBE Table 5 Security Type Codes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 29: Active Supervisory Signal Mode Of Operation

    (indicated by the “System Normal” message). The control panel sends a “System Normal” message to the LCD display, History buffer and installed printers, terminal mode LCD-80s, and CRT-2s. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 30: If Non-Latching Type Code Displays

    LED and activates CBE SUPERVISORY SUP.L(ION) Ion detector that indicates supervisory (non-alarm) condition Lights LED and activates CBE SUPERVISORY *Not suitable for Canadian applications. Table 6 Supervisory Type Codes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 31: Pre-Alarm Warning Mode Of Operation

    The Pre-Alarm function provides one of two levels of Pre-Alarm as follows: Note: For detailed information on Pre-Alarm applications, refer to the NFS-640 Programming Manual. • Alert – a non-latching condition that causes a Pre-Alarm when a detector reaches the programmed Pre-Alarm level.
  • Page 32: Disabled Points Mode Of Operation

    INTENSIVE CARE UNIT EASTERN WING 03:20P 071401 1M159 Extended 12 character Address of the Time and date of trouble custom label disabled device Figure 14 Sample Disabled Point Message NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 33: Non-Alarm Mode Of Operation

    In this case, when the point activates the control panel activates the point’s CBE to turn the lights down without any audio or visual indication on the control panel. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com...
  • Page 34: Active Trouble Monitor Mode Of Operation

    When the trouble condition is corrected, the panel will return to normal operation (indicated by the “System Normal” message). The control panel sends a “System Normal” message to the LCD display, History buffer and installed printers, terminal mode LCD-80s, and CRT-2s. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 35: Output Circuit Trouble Mode Of Operation

    * Type Code is Control Module type code only. ** Type Code is Panel/NAC Circuit type code only. Table 9 Control Module and Panel/NAC Circuit Trouble Type Codes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 36: How The Control Panel Indicates A Nac Trouble

    TROUBL CONTROL MODULE ADDR 1M044 OPEN 09:38A 071401 1M044 Device Address Type of Trouble Time and date of trouble Figure 19 Sample of a Control/Relay Module in Trouble Message NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 37: How To Respond To A Nac, Panel Circuit Or Control/Relay Trouble

    When the trouble condition is corrected, the panel will return to normal operation (indicated by the “System Normal” message). The control panel sends a “System Normal” message to the LCD display, History buffer and installed printers, terminal mode LCD-80s, and CRT-2s. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 38: Operation Of Special System Timers

    Increments the Alarm Verification counter (up to and a fire alarm no longer exists 99) for the device and returns to normal operation Table 10 Alarm Verification Timer Operation Continued on the next page... NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 39: Silence Inhibit Timer

    If a monitor module programmed with a Type Code initiates a fire alarm, the control panel WATERFLOW disables the key and the Auto Silence Timer. Refer to the NFS-640 Installation Manual SIGNAL SILENCE for information on Waterflow circuits. Style 6 and Style 7 Operation Style 6 and Style 7 are supervised methods of communicating with addressable devices.
  • Page 40 Notes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 41: Introduction

    From the “Entry” screen, press the 2 key. The control panel displays the “Read Status Options” screen as shown below:. READ POINT=0 HIST=2 ALARM HIST=4 <ENTER> PRNT POINT=1 HIST=3 ALARM HIST=5 <ENTER> NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 42: Viewing And Printing A Read Status

    In Read Status, you can also do the following: • Press the key to delete the previous entry. • Press the S key to abort Read Status. YSTEM ESET NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 43: How To View Read Status Of Devices, Zones, And System Settings

    When you select a device or a zone, the control panel displays information for the device or zone, but does not send this information to the serial ports or the History buffer. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com...
  • Page 44: How To View Read Status For A Detector

    Pre-Alarm sensitivity level The Pre-Alarm Sensitivity (1-9; 0 = Pre-Alarm not used) entered in the Detector Settings Screen. Note: Refer to “Detector Sensitivity Settings” in the NFS-640 Programming Manual for more information on the Pre-Alarm and Alarm Sensitivity settings •...
  • Page 45: How To View Read Status For A Control/Relay Or Monitor Module

    (Normal, Alarm, or Test). • Type Code The software Type Code that identifies the type of module. (Refer to “Point Programming” in the NFS-640 Programming Manual.) • CBE list Only the first zone in the device’s CBE list will be displayed.
  • Page 46: How To View Read Status For A Nac Or Panel Circuit

    • Type Code The software Type Code that identifies the type of NAC or Panel Circuit. Refer to “Appendix F - Type Codes” in NFS-640 Programming Manual. • CBE List Only the first zone in the NAC or Panel circuit’s CBE list will be displayed here.
  • Page 47: How To View Read Status For A Software Zone (Z01-Z99)

    Zone label for Releasing Function OFF RELEASE FUNCT RELEASE CONTROL DELAY=00 ABORT=ULI CROSS=N SOK=0000 R00 Selections for Indicates Special Zone R0 Releasing Zone R0 Figure 26 Sample Releasing Zone Read Status Display NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 48: How To Read Status For System Functions

    6 – both Style 6 and Style 7 SLC ACS=N Use ACS Selection N – No annunciator selected or Groups Y – Select and display ACS Selection Groups Table 11 System Function Parameters NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 49: How To Read Status For Annunciator Selections

    Annunciator addresses 1 to 19 can be programmed to any one of the above selections. If there is a UDACT, selections A-M will be sent to Annunciator addresses 20 to 32 respectively. Table 12 ACS Selection Groups NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 50: How To Read Status For Battery Levels

    Annunciators set to annunciator address 3 (A3) display the status of the panel circuits (ACS Selection Group M) How to Read Status for Battery Levels Pressing the key on the NFS-640 keyboard displays information concerning the BATTERY LEVEL state of the battery. A sample LCD display is shown below: Battery Voltage 27.8V...
  • Page 51: How To View Read Status For Event And Alarm History

    Type of event Program Change option used PROGRAM CHANGE 5=ZONE LABEL CHG 01:51P 071401 Sat Time and date of the event Figure 34 Sample Program Change Event Display NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 52: How To View Read Status For Alarm History

    ALARM: PULL_STATION INTENSIVE CARE UNIT EASTERN WING Z004 03:10P 071401 2M147 SLC address of the Time and date of the alarm device that alarmed Figure 36 Sample Alarm Event Display NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 53: How To Print Points, Event And Alarm History

    ********************ALARM HISTORY START **************************************** ALARM: SMOKE (ION) DETECTOR ADDR 1D075 Z002 02:28P 012201 1D075 ALARM: SMOKE (ION) DETECTOR ADDR 1D076 Z002 02:28P 012201 1D076 ******************* PRINT END **************************************** NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 54: How To View And Print Hidden Event And Alarm History

    Read Hidden History “How to View Read Status for Event History” on page 51 Print Hidden History “How to Print Event History” on page 53 Table 13 Hidden History Selections NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 55: Overview

    Special Zone Refer to Page Releasing Zones (R0-R9) R0-R9 Time, Date, and Holiday Functions F5, F6, F7 NAC and Panel Circuit Coding Presignal and Positive Alarm Sequence (PAS) Operation NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 56: Releasing Zones (R0-R9)

    This section contains descriptions of each Releasing Function option and an example of how Releasing Zone options work. For instructions on programming Releasing Functions, refer to the NFS-640 Programming Manual. Each Releasing Zone includes the following releasing options:...
  • Page 57: How Releasing Zones Operate

    2D102 2D104 CBE list = Z01 ZR1 CBE list = Z01 ZR1 Releasing Zone ZR1 Figure 43 Illustrated Example of Cross Zone Programming Continued on the next page... NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 58 ZR1 in their CBE. Cross=H Activation of heat detector 2D104 and one smoke detector (2D101, 2D102, or 2D103). Table 15 Example of Cross Zone Selections NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 59: Time, Date, And Holiday Functions

    You can use the Read Status Entry option to view the current selection for the Time function. To do so, press the following keys in sequence: Note: For instructions on programming the Time function, refer to the NFS-640 Programming Manual. The LCD display shows the current selections for the Time Control function. The figure below shows a...
  • Page 60: How To View Holiday Function Selections

    You can use the Read Status Entry option to view the current selection for the Holiday function. To do so, press the following keys in sequence: Note: For instructions on programming the Holiday function, refer to the NFS-640 Programming Manual. The LCD display in Figure 46 gives an example of an LCD display of a Holiday function:...
  • Page 61: Nac And Panel Circuit Coding

    You can use the Read Status Entry option to view the current selection for the Coding function. To do so, press the following keys in sequence: Note: For instructions on programming the Coding function, refer to the NFS-640 Programming Manual. The LCD display shows the current selections for the Code Type. Figure 47 shows a sample LCD...
  • Page 62: Presignal And Positive Alarm Sequence (Pas) Operation

    PAS (15 s) If PAS=Y, alarm activates outputs if not acknowledged Initial alarm Alarm activates outputs, annunciation if panel is not reset. Figure 48 Presignal and PAS Time NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 63: How To View Presignal And Pas Selections

    You can use the Read Status Entry option to view the current selection for the Presignal function. To do so, press the keys in sequence: Note: For instructions on programming the Presignal function, refer to the NFS-640 Programming Manual. The LCD display shows the current selections for the Presignal function. The figure below shows a...
  • Page 64: How To Respond To An Alarm With A Presignal Delay Timer (Pas Selected)

    The Manual Evacuate screen and Alarm screen display alternately at 3-second intervals. If the Presignal Delay Timer reaches its programmed value, without operator intervention, the control panel activates all outputs programmed to F0. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 65: Appendix B: Intelligent Detector Functions

    Appendix B: Intelligent Detector Functions Note: For instructions on selecting Intelligent Detector Functions, refer to the NFS-640 Programming Manual. Descriptions for Intelligent Detector Functions Function Description Analog Display The control panel reads and displays analog information from the 318 analog detectors (159 per SLC). The display shows the sensed air at the detector as a percentage of the alarm threshold for each detector.
  • Page 66 Notes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 67: Appendix C: Remote Terminal Access

    The control panel can communicate with a remote terminal or computer connected to the EIA-232 PC/ Terminal port. Refer to the NFS-640 Installation Manual for installation information. Note: See the NFS-640 Programming Manual for instructions on enabling the CRT. This port may be set up for interactive operation or for monitoring only. Interactive operation requires that all equipment be UL-listed under UL Standard for Safety UL 864 and be installed and set up as directed under Local Terminal Mode (LocT) or Local Monitor Mode (LocM).
  • Page 68: Local Terminal Mode (Loct)

    • Clear the entire History buffer. • Set the AWACS alert and action levels. Control Functions • Acknowledge. • Signal Silence. • System Reset. • Drill. Table 19 Local Terminal Mode Functions NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 69: Local Monitor Mode (Locm)

    • Clear the entire History buffer. • Set the AWACS alert and action levels. Control • Acknowledge Functions • Signal Silence • System Reset • Drill Table 20 Local Monitor Mode Functions NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 70: Remote Terminal Mode (Remt)

    • Display a list of all programmed points in the system. • Step through the History buffer event by event. • Display the entire History buffer. Alter Status Control Functions Table 21 Remote Terminal Mode Functions NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 71: Using The Crt-2 For Read Status

    Using the CRT-2 for Read Status Overview This section shows how to perform Read Status functions from a CRT-2. Note: See the NFS-640 Programming Manual for instructions on enabling the CRT port. For more information see the “Read Status” section of this manual. Function Lets you...
  • Page 72: Read Point

    DETECTOR ADDR 1D001 Z03 INVALID REPLY 01;09P 011399 1D001 TROUBL SMOKE(ION) DETECTOR ADDR 1D002 Z02 INVALID REPLY 01;09P 011399 1D002 TROUBL SMOKE MONITOR MODULE ADDR 1M002 Z04 INVALID REPLY 01;09P 011399 1M001 NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 73: Display The Status Of All Programmed Points

    The first line that appears displays the number of events in the History buffer. Step through the Alarm History buffer one event at a time by pressing the Next F5 or Prior F6 function keys. NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com...
  • Page 74: Send The Alarm History Buffer To The Crt-2

    10:21A 050501 1M065 ALARM: MAN_RELEASE MODULE ADDR 1M065 10:19A 050501 1M065 ALARM: MAN_RELEASE MODULE ADDR 1M065 03:20P 050401 1M065 ALARM: SMOKE (ION) DETECTOR ADDR 1D129 03:20P 050401 1D129 NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 75: Using The Crt-2 For Alter Status

    This section shows how to do Alter Status functions from a CRT-2 Note: The panel must be in Local Terminal Mode (LocT) or Local Monitor Mode (LocM). Note: See the NFS-640 Programming Manual for instructions on enabling the CRT port. Function Lets you...
  • Page 76: Enable Or Disable Detectors, Modules, Or Panel Circuits

    D101 Now Enabled, Enter E(Enable) / D(Disable) or Esc. to Abort Press D to Disable (E to Enable); then press ENTER Press Device now disabled TROUBL SMOKE(PHOTO) DETECTOR ADDR 101 Z03 DEVICE DISABLED 08:29A Wed 07/07/99 D101 NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 77: Change Alarm And Pre-Alarm Levels

    Press STATUS CHANGE Clear verify count 09:37A Wed 07/07/99 Clear the Entire History Buffer Clear History lets you clear the entire History buffer: Press ************** History Clear *************** NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 78: Set The Pre-Alarm For Alert Or Action

    “Alert” to “Action” as follows: Press Set Pre-alarm Alert(NO)/Action(YES). Type N or Y then Enter STATUS CHANGE Change Alert/Action 09:37A Wed 07/07/99 Press Pre-alarm now set for ACTION NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 79: Appendix D: Point And System Troubles Lists

    (such as someone smoking) that causes it to go into verification frequently. XP TBL XPIQ general trouble. Check the XPIQ point for problems Table D.1 Point (Device) Troubles NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 80: System Troubles

    Style 6 trouble until you correct the condition and press reset. Style 7 configuration of the SLC requires the use of ISO-X modules. UDACT NO ANSWER The UDACT is not responding. UDACT TROUBLE The UDACT is in trouble. Table D.2 System Troubles NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 81 Notes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 82 Notes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 83 Notes NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 84 30 trouble monitor type codes 34 Date Functions 59 Day/Night Sensitivity Operation 65 NAC Circuit Trouble DCM-4RK 35 panel indication 36 Delay Timer 56 NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 85 Supervisory 30 software zones 47 Trouble 34 Special Zone (F0-F9) 47 System Functions 48 total of installed devices 43 using a CRT. See Appendix C VCM-4RK 35 NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 86 INDEX Verification Counter 77 Warning When used for CO2 releasing applications... 21 Waterflow Circuit operation 39 XP5-C transponder points 35 XPC transponder points 35 NFS-640 Operations Manual P/N 51334:B 10/03/2003 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 87 Products are date stamped at time of manufacture. The sole and exclusive obligation of NOTIFIER® is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service. For products not under NOTIFIER®...
  • Page 88 NOTIFIER is a company. World Headquarters 12 Clintonville Road Northford, CT 06472-1653 USA 203-484-7161 fax 203-484-7118 www.notifier.com Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...