Appendix D: CBE (Control-By-Event)

Equation Entry

The equations must be entered using the VeriFire™ Tools Program Utility. All are subject to the maximum
number of arguments possible in a logic instruction as discussed above (Item Number 9 on page 95).

Logic Functions

The "AND" Operator

Requires that each argument be in alarm.
Example: AND(Z02,Z05,Z09)
All three arguments in the equation must be in alarm for the output point to be activated

The "OR" Operator

Requires that any argument be in alarm
Example: OR(Z02,Z05,Z09)
If any one of the three arguments in the equation is in alarm the output point will be activated.

The "NOT" Operator

Inverts the state of the argument (activated to deactivated OR deactivated to activated).
Example: NOT(Z02)
The output point will remain activated until the argument goes into alarm.
If the argument goes into alarm the output point will deactivate.

The "ONLY1" Operator

Requires that only one argument be in alarm.
Example: ONLY1(Z02,Z05,Z09)
If only one of the arguments is in alarm the output point will be activated.

The "ANY2" Operator

Requires that two or more arguments be in alarm.
Example: ANY2(Z02,Z05,Z09)
If any two or more of the arguments are in alarm the output point will be activated.

The "ANY3" Operator

Requires that three or more arguments be in alarm.
Example: ANY3(Z02,Z05,Z07,Z09)
If any three or more of the arguments are in alarm the output point will be activated.

The "XZONE" Operator

Requires that any combination of two or more input devices programmed to a zone be in alarm.
Example: XZONE(Z02)
If any combination of two or more initiating devices that have been programmed (CBE) to this software
zone comes into alarm, then this output point will be activated.

The "RANGE" Operator

Each argument within the range must conform to the requirements of the governing operator. The range
limit is 20 consecutive arguments.
Example: AND(RANGE(Z1,Z20))
Zone 1 through Zone 20 must all be in alarm for the output point to be activated.