VISTA-10SEa Installation and Setup Guide
SYMPTOM
4. Periodic beep(s) from
keypad.
5. With 5800 RF System, no
response to a transmitter in
normal operation, although
zone number clears during
Transmitter Sniffer mode.
6. Nuisance or phantom
alarm.
7. Intrusion alarm for no
apparent reason.
8. Repeated "Low-Battery"
signal.
9.
"CHECK" and "09"
displayed.
SYMPTOM
1. "NO AC" displayed.
2. Digital communicator
message not being
received.
3. Does not arm properly.
16-2
POSSIBLE CAUSE
4a. System is in Test mode.
4b. A wireless transmitter low battery has
occurred and is displayed.
4c. A supervision CHECK has occurred.
Put control in Test mode. If zone does not re-
spond, try operating the tamper switch or an-
other input to the transmitter.
5a. If another input causes the zone to be dis-
played, the wrong loop input was entered
when programming.
5b. If no response at all from this transmitter,
this physical transmitter has not been
entered into the system.
6a. Sensors not properly installed, wired, or
monitored.
6b. Universal transmitter (5817) programmed
incorrectly.
7a. Protected door or window opened while
system is armed.
7b. Improper user operation of exit/entry de-
lays.
7c. Magnets located too far from switches,
and/or doors and windows not properly
aligned.
7d. Magnetic contacts improperly connected
or wire broken.
7e. Entry door programmed as "Instant."
7f.
Loose-fitting door or window being rattled
by wind or vibrations.
8a. Transmitter located where temperature
drops below 0°C.
8b. Poor quality or unspecified battery in
transmitter.
8c. Transmitter malfunctioning.
10. Communication between control and zone
expander or wireless receiver is interrupted.

CONTROL

POSSIBLE CAUSE
1a. Interrupted mains power supply.
2a. Control in Test mode.
2b. Telephone connection not secure.
2c. Digital communicator malfunctioning.
2d. Telephone number in program needs prefix
or access code.
2e. Telephone call to central monitoring station
requires operator assistance.
3a. READY light not on.
REMEDY
4a. Enter [Code] + OFF to exit Test mode.
4b. Enter [Code] + OFF and replace the battery.
4c. Check the wireless transmitter indicated.
Restore communication to the RF receiver
to cancel the condition.
5a. Delete input's serial number (not the zone),
and enter the proper loop input (see field
56 or
83).
*
*
5b. Determine which transmitter is programmed
for this zone and reprogram as necessary.
6a. Check installation to see if in accordance
with established procedure.
6b. Check programming for transmitter.
7a. Check with occupants of protected premises
in case protected door or window was
opened unintentionally during armed period.
7b. Check programming of entry delays.
7c. Check all openings for proper switch and
magnet orientation.
7d. Check wiring connections. Be sure wires are
properly stripped and are tightly fastened to
screw terminals.
7e. Check and revise programming.
Reprogram transmitter number.
7f.
Mount magnet closer to mating switch.
8a. Change location. Use magnetic contacts to
protect opening.
8b. Check battery. Use only batteries specified
(does not apply to transmitters with non-
replaceable batteries).
8c. Replace faulty transmitter.
10. Check wiring connections of expander and
receiver to control. Check DIP switch
settings on the units.
REMEDY
1a. Check transformer connection and power
line circuit breaker. Transformer must be
connected to an unswitched (24-hour)
outlet.
2a. Remove from Test mode.
2b. Check all connections.
2c. Check with a different VISTA-10SEa.
2d. Program prefix or access code into the
control.
2e. System cannot work in this situation.
3a. Check for faulted non-exit route zone(s)
by pressing [ ] ; make faulted zone(s)
intact, or use Bypass arming, if desired.