VISTA-10SEa Installation and Setup Guide
power (e.g., System Sensor No. A77-716B Relay module) to the smoke detectors.
Remove the 1000-ohm EOL resistor if connected across zone 5 terminals. You must connect the
EOL resistor across the loop wires at the last detector.
Programming Basic Wired Zones
1. With at least one 2-line alpha keypad (6139) connected to the keypad terminals on the
control, power up the system temporarily. If you previously connected the plugpack to the
control panel, you need only plug it in to AC mains to power up the system.
2. Enter the Programming mode by keying the following on the alpha keypad: Installer
code (4 1 1 1) + 8 + 0.
Data fields 22 RF SYSTEM and 25 WIRED EXPANSION/RELAY USED must be programmed
as required before continuing.
3. Press
program zone numbers, zone types, and Alarm Report codes for wired zones.
NOTE: If you enabled the 5800 Wireless System in field
4-2
+
AUX PWR
OUTPUT
-
TERMINALS
TO HI SIDE
OF ZONE 5
+
(TERM 14)
HEAT
-
DETECTOR
TO LO SIDE
OF ZONE 5
(TERM 15)
Figure 4–1. 4-Wire Smoke Detector Connections to Zone 5
Compatible System Sensor 4-Wire Smoke/Combustion Detectors Table
Model
Description
1412
4-wire ionisation products of combustion detector.
A77–716B
EOL relay module (supervisory module for wired 4-wire fire
zone).
2112/24T
Low-profile 4-wire photoelectric smoke detector with 135º F
(57º C) heat detector.
56. Note that this is an Interactive programming mode. You will use it to
screen prompt will be "Program Tool?... 0 = No 1 = Yes." Enter 0 (No). The
next prompt will ask you to enter zone number.
4-WIRE SMOKE
DETECTORS
+
+
-
HEAT
DETECTOR
-
+
BLK
•
•
EOL
POWER
•
•
SUPERVISION
RELAY
VIOLET
-
MODULE
A77-716B
•
1000
OHMS
EOLR
•
22 (a "1" entry), the first