Programming Wired Expansion Zones

1. With at least one 2-line alpha keypad (6139) connected to the keypad terminals on the
control, power up the system temporarily. If you previously connected the plugpack to
the control panel, you need only plug in it in AC mains to power up the system.
2. Enter the programming mode by keying the following on the alpha keypad: Installer
code (4 1 1 1) + 8 + 0.
If the system is using RF zones or wired expansion, you must program data fields 22 RF
SYSTEM TYPE and 25 WIRED EXPANSION/RELAY USED as required before continuing (see
Programming Form in the separate Programming Guide ).
3. Press 56. Note that this is an Interactive programming mode. It is used to program
zone numbers, zone types, and alarm report codes for all zones that are going to be used.
NOTE: If you enabled the wireless system in field 22 (a "2" for 5800), the first screen
4. Enter 0 (No). The next prompt will ask you to enter a zone number.
Enter Zn Num.
(00 = Quit)
Zn ZT
10 00 – 00 RF: 1
5-2
RELAY
RELAY
2
CONNECTOR
}
RELAY
NO C NC
}
TAMPER JUMPER POSITION
4229 IN CABINET
(NOT TAMPERED)
4229 REMOTE
(TAMPER PROTECTED)
1
RLY
RLY
2
1
REED
(TAMPER)
RELAYS
SWITCH
"OFF"
1K
A
ZONES:
Figure 5–1. Wiring Connections, 4219 & 4229 (4229 shown)
prompt will be "Program Tool?... 0 = No 1 = Yes" (if 5800 was selected).
10
Zone Number 
RC
In
L
DIP SWITCH
FOR SETTING ADDRESS
AND ZONE "A" RESPONSE
EITHER OR BOTH CAN BE USED
1
4-PIN CONSOLE PLUG
TB1
2
3
4
5
6
7
8
9
10 11 12
B
C
D
E
F
G
Enter
the
first
zone
program (or 00 to exit zone programming). Normally, you will
be starting with zone 10 (this is the default).
Press [ ] to continue.
A summary display will appear, showing the present status
of that zone's programming.
Zn = zone number.
ZT = zone type.
RC = report code for that zone.
In = input type of zone (AW for Aux Wired).
L = loop (not used for wired expansion zones).
Values in the summary display are the currently programmed
values.
To start programming zone 10, press [ ]. A prompt for zone
type will appear.
4229
TB2
GRN DATA OUT
4
TO CONTROL
BLK
3
(–) GROUND
4
3
RED
(+) 12VDC
2
2
YEL DATA IN
1
1
FROM
CONTROL
TERMINATE EACH
PROGRAMMED ZONE
WITH 1000 OHM (1K)
END-OF-LINE RESISTOR
(EACH ZONE'S MAX.
LOOP RESISTANCE:
300 OHMS + E.O.L.)
H
number
that
TERMINALS ON
CONTROL PANEL
(TERM 6)
(TERM 4)
(TERM 5)
(TERM 7)
you
wish
to