Basic Wired Zones 1-6; Installing The Basic Wired Zones; Wiring Burglary And Panic Devices To Zones 1-6; Wiring 4-Wire Smoke/Combustion Detectors On Zones 5 - ADEMCO Vista-10SEa Installation And Setup Manual

Vista-10sea
Hide thumbs Also See for Vista-10SEa:
Table of Contents

Advertisement

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
In This Section

Installing the Basic Wired Zones

Wiring Burglary and Panic Devices to Zones 1-6

Wiring 4-Wire Smoke/Combustion Detectors on
Zone 5
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
Installing the Basic Wired Zones
Common Characteristics for Zones 1–6
Response time from 400 milliseconds, nominal.
Zone 3 can be programmed (in field
(10mSec max) to an open (suitable for vibration-type sensors).
400mSec nominal, which should be used for most sensors.
EOLR-supervised zones supporting both open-circuit and closed-circuit devices.
As many 4-wire smoke detectors as can be powered from Aux Power on the control (in
zone 5).
Wiring Burglary and Panic Devices to Zones 1–6
1. Connect sensors/contacts to the wired zone terminals 8–16 (zones 1-4 and zone 6). See the
Summary of Connections diagram.
2. Connect closed-circuit devices in series in the high (+) side of the loop. The EOL resistor
must be connected in series with the devices, following the last device. See the Summary
of Connections diagram.
3. Connect open-circuit devices in parallel across the loop. The 1,000-ohm EOLR must be
connected across the loop wires at the last device.
If the EOLR is not at the end of the loop, the zone will not be properly supervised, and the system
may not respond to an open circuit in the zone.
Wiring 4-Wire Smoke/Combustion Detectors on Zone 5
The system will support as many 4-wire detectors as can be powered from Auxiliary Power
on the control in zone 5. Refer to the detector's instructions for complete details regarding its
proper installation and operation.
1. Connect 12-volt power for the detectors from Auxiliary Power terminals 4 and 5 (which
will interrupt power for fire alarm reset). Observe proper polarity when connecting
detectors. See Figure 4-1.
2. Connect detectors (including heat detectors, if used) across terminals of zone 5. All
detectors must be wired in parallel. You should use a supervisory module to supervise

Basic Wired Zones 1-6

Programming Basic Wired Zones
Checkout Procedure for Basic Wired Zones (1-6)
52) for normally-closed sensor fast response
S E C T I O N
Default response is
4
4-1