Checkout Procedure for Wired Expansion Zones

After you have completed installation of all devices, check all wired expansion zones as
follows:
1. Make certain that all devices and sensors connected to the wired expansion zones are not
in a faulted state. Doors and windows with contacts should be closed, PIRs should be
covered (use a cloth to mask them temporarily if necessary).
2. With all zones intact (including basic wired zones), the alpha keypad connected to the
system should display:
If the keypad displays this:
press [ ] to display the faulted zone(s). Restore any faulted zone(s) as necessary.
When the "READY TO ARM" message is displayed, you can proceed to the next step.
3. Fault and restore every contact or sensor in each expansion zone individually to ensure
that it is being monitored by the system. Each time a zone is faulted, the keypad should
display the number of the faulted zone (as programmed by you just previously in 56
mode). When each zone is restored, the "READY TO ARM" message should appear again.
4. When you get the proper displays on the keypad(s), the wired expansion zones in the
system are functioning properly.
If the keypad displays a "CHECK 09" message, data from the control is not being received by the
zone expander module. Check your wiring and DIP switch settings.
5-4
DISARMED
READY TO ARM.