Installing The 5800Tm Module; Terminal Connections Table - ADEMCO Vista-10SEa Installation And Setup Manual

Vista-10sea
Hide thumbs Also See for Vista-10SEa:
Table of Contents

Advertisement

determining mounting location outside of the cabinet.
2. Make sure that the receiver's DIP switches are set for device address "0," as shown in
Figure 5-1 (all switches to the right: OFF).
3. Connect the receiver's wire harness to the control's keypad terminals (4, 5, 6, and 7).
Plug the connector at the other end of the harness into the receiver (see Figure 6-1).
Refer to the receiver's installation instructions for further installation instructions regarding
antenna mounting, etc.
NOTE: IF THE CIRCUIT BOARD IS MOUNTED IN
CONTROL'S CABINET, GROUNDING LUGS (2)
PROVIDED MUST BE INSERTED IN LEFT-
HAND TERMINALS OF ANTENNA BLOCKS AND
SECURED TO CABINET (SEE RECEIVER'S
AND CONTROL'S INSTRUCTIONS)
TO RELEASE CIRCUIT BOARD,
REMOVE SCREWS (2)
AND BEND BACK TABS (2).
Figure 6–1. 5881 Series Wireless Receivers (cover removed)

Installing the 5800TM Module

Installation of this module is necessary only if you are using one or more 5827BD or 5804BD
Wireless Bi-directional keypads.
The 5800TM must be located approximately 0.5m from the 5881 receiver's antennas. The
5800TM must not be installed within the control cabinet.
accompanying mounting bracket.
5800TM Wiring Connections
Connect the 5800TM to the control panel's keypad connection terminals, using the supplied
connector with flying leads, as follows:
Do not cut any of the jumpers on the 5800TM when using it with the
VISTA-10SEa.
For additional information, refer to the 5800TM's instructions.
CIRCUIT
BOARD
MOUNTING
INTERFERENCE
HOLES
INDICATOR

Terminal Connections Table

WIRE
RED (+12VDC)
BLACK (Ground)
GREEN (Data to Control)
YELLOW (Data from Control)
BLUE: Not Used
Section 6: Wireless (RF) Zone Expansion
ANTENNAS
INSERT IN
RIGHT-HAND
TERMINALS
PLUG
&
SOCKET
DIP SWITCH
LED
TERMINAL ON CONTROL
Terminal 5
Terminal 4
Terminal 6
Terminal 7
YELLOW
}
RED
TO CONTROL'S REMOTE
BLACK
KEYPAD CONNECTION
GREEN
POINTS. EACH RECEIVER
WIRING
MUST BE ON INDIVIDUAL
OPENING
WIRE RUN.
KNOCKOUT
ON
OFF
AREA FOR
SURFACE
WIRING
Mount the unit using its
4
3
2
1
6-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents