VISTA-10SEa Installation and Setup Guide
RED JUMPER

Programming for External Sounders

1. With at least one 2-line alpha keypad (6139) connected to the keypad terminals on the
control, power up the system temporarily. If you previously connected the AC
transformer to the control panel, you need only plug in the AC plugpack (to a 230VAC
outlet) to power up the system.
2. Enter the Programming mode by keying the following on the alpha keypad:
code (4 1 1 1) + 8 + 0.
3. Press 28 Single Alarm Sounding per Zone/Armed Period.
Enter 1 for yes, 0 for no (default).
4. Press 29 Fire Sounder Timeout.
Enter 1 for no timeout, 0 for timeout (default).
5. Press 30 Siren Timeout.
Enter 0 for no timeout, 1 for 4 min, 2 for 8 min (default), 3 for 12 min, 4 for 16 min.
6. Press 51 Confirmation of Arming Ding.
Enter 0 for no (default); 1 for yes; 2 for yes, but with RF arming only.
7. Exit the Programming mode by entering 99.

Testing the Sounder

After installation of the sounder is completed, test the security system carefully, as follows:
1. Connect the battery wires from the control board to the battery, observing correct
polarity.
2. Enter the Installer code (4 1 1 1) and press the TEST key on the wired keypad.
The external sounder should sound for 1 second if the sounder is working and proper
connections have been made. Note that if the backup battery is discharged, the sounder
will not turn on.
3. To turn off the Test mode, enter the Installer code (4 1 1 1) and press the OFF key.
9-2
CONTROL BOARD
( + )
3
ALARM
OUTPUT
( - )
4
Figure 9–1. Typical Sounder Wiring
EXAMPLE:
No. 702 SIREN
( + )
1k OHM
EOL
RESISTOR
( - )
Installer