Hard Wired Zones; Basic Contm~S Zones - ADEMCO via30 Installation Instructions Manual

Table of Contents

Advertisement

20-
Arm-Stay
This is a special purpose zone type used with 5800 series wireless pushbutton or
contact closure or opening, and which will result in arming the system in the STAY
mode when the zone is activated.
21 - Arm-Away
This is a special purpose zone type used with 5800 series wireless pushbutton or
contact closure or opening, and which will result in arming the system in the
AWAY mode when the zone is activated.
22-
Disarm
This is a special purpose zone type used with 5800 series wireless pushbutton or
contact closure or opening, and which will result in disarming the system when the
zone is activated,
23-
No Alarm
This zone type can be used on a zone when an output relay action is desired, but
Response
with no accompanying alarm (ex. lobby door access).
By using a 4281/5881 RF Receiver and the appropriate 5700/5800 series
transmitters, all of the above zone types are available for the wireless portion of
the system.
HARD-WIRED
ZONES
Basic Control's Zones
The Ademco
via30 supports 2 hard-wired zones, which are connected as
zones 5 & 6. These zones must be EOLR supervised, and can use N.O. and/or
N.C. sensors.
Zone
Response
Type
Any zone response can be assigned to devices on
these zones.
Response
Time
300-500 msec.
I/lax. Zone
Resistance
300 ohms, excluding EOLR
EOLR
Supervised
Supports both open circuit and closed circuit
devices.
Connect open circuit devices in parallel across
the loop. The 1,000 ohm EOLR must be
connected across the loop wires at the last
device.
Important: If the EOLR is not at the end of the
loop, the zone is not properly supervised. The
system may not respond to an open circuit within
the zone.
Connect closed circuit devices in series with the
loop.
EOLR Fire Zone 5
Only zone 5 can be used for fire.
Supporls as many 4-wire smoke detectors as can
be powered.
The zones
must be configured
for EOLR
supervision.
The detectors must be wired in parallel, with the
EOLR at the last detector for full supervision.
To supervise power, a supewisory module (e.g.,
System Sensor No. BK-A7771 601 EOL Relay
Module) is required.