Configuring Temperature Sensors Thresholds
Click the temperature sensor thresholds link at the bottom of the Sensors page to display the configuration page:
To set temperature sensor thresholds:
1. Provide the threshold hysteresis between event state and recovery temperature. Range is 0-30° Celsius or
0-54° Fahrenheit; default is 1° Celsius or 2° Fahrenheit.
2. Set the low/high alarm and low/high warning threshold values for the temperature sensor(°). Range is
minimum -40° to maximum 123° Celsius or minimum -40° to maximum 253° Fahrenheit.
3. Click Apply.
Using the Web Interface
Smart PRO2 – User Guide
77