Configuring Phase Power Factor Thresholds
Click the phase power factor thresholds link at the bottom of the Phases page to display the configuration page:
To set phase power factor thresholds:
1. Provide a numeric value for the threshold hysteresis between event state and recovery. Range is 0-0.20;
default is 0.02.
2. Set numeric values for the low alarm/warning phase power factor thresholds. Range is min 0.00; max is
1.00.
3. Click Apply.
Using the Web Interface
Smart PRO2 – User Guide