Configuring Cord Apparent Power Thresholds
Click the apparent power thresholds link at the bottom of the Cords page to display the configuration page:
To set apparent power thresholds:
1. Provide the threshold hysteresis between event state and recovery (VA). Range is 0-1000VA; default is
100VA.
2. Set the low/high alarm and low/high warning threshold values (VA). Cord apparent power includes power
factor. Range is min 0VA; max is power capacity shown in cstat command.
3. Click Apply.
Using the Web Interface
Smart PRO2 – User Guide
•
53