Configuring Line Current Thresholds
Click the thresholds link at the bottom of the Lines page to display the configuration page:
To set line current thresholds:
1. Provide the threshold hysteresis between event state and recovery (A). Range is 0.0-10.0A; default is 1.0A.
2. Set the low/high alarm and low/high warning current load threshold values (A). Range is min 0A; max is
current limit displayed in show lines command.
3. Click Apply.
Using the Web Interface
Link to return to the Lines configuration page
Smart PRO2 – User Guide
•
65