set phase

Command Syntax
Parameters
Sub-Parameters
Command Access
Using the Command Line Interface (CLI)
Sets phase configuration values.
set phase email [disabled | enabled] <name | id | ALL>
set phase pf [alarmlo | warnlo] <name | id | ALL> <value>
set phase snmpt [disabled | enabled] <name | id | ALL>
set phase volts [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set phase volts hyst <value>
For AC products only:
set phase pf hyst <value>
The set phase command uses the following parameters:
email
Sets email notifications for phase events.
hyst
Sets hysteresis between event state and recovery.
pf
Sets power factor. min 0.00, max 1.00, hyst 0.0-20.0 (default 0.02).
snmpt
Sets SNMP trap notifications for phase events.
volts
Sets voltage. min and max vary by product
the min-max range, issue set cord nomvolts all command (press ESC to
quit command).
The set phase command uses the following sub-parameters:
alarmhi
Sets high alarm value.
alarmlo
Sets low alarm value.
warnhi
Sets high warning value.
warnlo
Sets low warning value.
Admin level only
Smart PRO2 – User Guide
*
,
hyst 0.0-20 (default 0.02). * For
163