Configuring Outlet Current Thresholds
Click the current thresholds link at the bottom of the Outlets page to display the configuration page:
To set outlet current thresholds:
1. Provide threshold hysteresis between event state and recovery (A). Range is 0.0-10.0A; default is 1.0A.
2. Set the low/high alarm and low/high warning threshold values (A) for outlet current load. Range is min 0.0A;
max is max current shown in show outlets command.
3. Click Apply.
Using the Web Interface
Smart PRO2 – User Guide
67