Summary of Contents for Server Technology PRO2 Switched POPS STV-6542
Page 1
Switched PRO2 User Guide Firmware 8.0 Switched PRO2 – User Guide • Introducing the PRO2...
Page 2
The Globe logo is a trademark of Server Technology, Inc., registered in the US. Use of the logos for commercial purposes without the prior written consent of Server Technology may constitute trademark infringement and unfair competition in violation of federal and state laws.
Table of Contents Chapter 1: Introducing the PRO2 Welcome to the Server Technology Switched PRO2 ........5 What’s the PRO1? ....................6 About Your User Guide ..................7 PDU Power Pivot ....................7 Star Linking Technology ..................8 Unit Persistence ....................
Page 4
Chapter 5: Using the Command Line Interface (CLI) Logging In ......................130 Quick Tour of the Command Line ..............130 List of Commands .................... 133 Command Details ..................... 139 Appendix A: Product Support Information LED Indicators ....................204 Branch Circuit Protection ................205 Circuit Breaker ....................
Welcome to the Server Technology Switched PRO2 The Switched PRO2 is the latest design in Server Technology’s reliable power distribution units, providing flexibility for future power management, cost savings, and advanced solutions for data center customers. Key Product Features...
What’s the PRO1? Like the PRO2, the PRO1 (Switched and Smart) is another new PDU design from Server Technology to provide the same type of flexibility for power management, cost savings, and advanced data center solutions that the PRO2 delivers.
About Your User Guide This user guide was designed for data center personnel who monitor power, control outlet actions, and administer equipment operations in the data center network using Server Technology’s firmware, version 8.0x or later, on the PRO2 product family.
Star Linking Technology Server Technology’s PRO2 introduces Star Linking technology that supports the optional linking of up to three expansion (link) units per one PRO2 master unit, allowing a single IP address for multiple cabinets. Note: The Star Linking feature is available only with PRO2 products.
Module Port Getting Started The optional Star Linking feature is sold as a separate kit purchased from Server Technology. To use the feature, contact your sales representative to order the PRO2 Multi-Linking Module Kit, part number KIT-PRO2LINK-01M. The kit contains:...
Experience Server Technology's FREE Technical Support Server Technology understands that there are often questions when installing and/or using a new product. Free Technical Support is provided from 8 a.m. to 5 p.m. PST, Monday through Friday. After-hours service is provided to ensure your requests are handled quickly no matter what time zone or country you are located in.
Equipment Overview The following illustration highlights the key operational areas of the Switched PRO2 unit: Switched PRO2 – Equipment Overview Switched PRO2 – User Guide • Introducing the PRO2...
Chapter 2: Installing the PRO2 Before installing your Switched PRO2 unit, look over the following lists to make sure you have all the items shipped with the unit, as well as any other items needed for proper installation. Standard Accessories Mounting Hardware •...
Safety Precautions This section contains important safety and regulatory information that must be reviewed before installing and using the Switched PRO2. Only for installation and use in a Destiné à l'installation et l'utilisation dans le Nur für Installation und Gebrauch in Restricted Access Location in cadre de Restricted Access Location selon eingeschränkten Betriebszonen gemäß...
Input Power Cord Retention Options for PRO2s with IEC C20 Inlets Determine which Detachable Input Cord was supplied with your PRO2 unit: For the following Detachable Input Cords with the self-locking IEC C19 feature, follow Procedure A below. PTCORD-L1, PTCORD-L2, PTCORD-L3, PTCORD-L5, PTCORD-L6, or PTCORD-L7.
Attaching Safety Earth Ground Connection Server Technology PDUs are supplied with an external safety ground connection to provide an alternate ground path for fault currents, and to maintain the same ground reference between it and the equipment rack. NOTE: The auxiliary external ground location may vary. Most PDUs will have it located near the power cord entry located near the symbol.
Mounting the PRO2 Unit The following illustration shows how to mount the PRO2 unit in vertical or horizontal orientation: Horizontal/Rack 1. Select the appropriate bracket mounting points for proper mounting depth within the rack. 2. Attach the L-brackets to these mounting points with two screws for each bracket. 3.
Page 17
1. Keep the on/off switch on the device in the off position until after it is plugged into the outlet. 2. Connect the devices to the PRO2 outlets. Note: Server Technology recommends even distribution of attached devices across all available outlets to avoid exceeding the outlet, branch, or phase limitations.
Network Defaults The PRO2 is configured with the following network defaults to allow unit configuration out-of-the-box through either Telnet or Web. However, note that when the PRO2 is installed on a DHCP-enabled network, the following network defaults do not apply because the PRO2 ships with DHCP support enabled by default. Network Defaults (for non-DHCP-enabled networks): IP Address: 192.168.1.254...
This chapter introduces several key features of the firmware (version 8.0x or later) for the PRO2. Note: Firmware, version 8.0, for the PRO2 product is not compatible with other Server Technology Rack Power Distribution Unit products. There is no upgrade path from earlier PDI products to PRO2 products.
PRO2 Dashboard View The firmware Overview > System page provides a fast and high-level view of the overall condition of the PRO2 unit. The sub-system status view shows the current operational state of individual PRO2 (units, cords, lines, etc.). The color-coded status icon for each area is hot-linked to the corresponding monitoring page to show the operating details behind the status, for example: Switched PRO2 –...
Spaces Allowed Usernames 1-32 characters Passwords 1-32 characters Note: For security, Server Technology recommends first creating a new user account with administrative rights, and then removing the default admn account. Switched PRO2 – User Guide • Getting Started with the Firmware...
User Access Rights The following table defines the user rights granted by the administrative user for access to PRO2 operations using either the Web GUI or the Command Line interface (CLI). Only the options for which the user has access rights will be available in the firmware for the user.
IP address is provided. Server Technology uses IPv6 “dual stack” support in the firmware PRO2 product line. IPv6 has been designed to succeed IPv4 as the dominant communications protocol for internet traffic, to avoid depletions of the IPv4 address space, and to allow more IP address growth.
Network-Enabled Modes Notes: • For all network-enabled modes described below, the PRO2 will set an auto-configured IPv6 address, and if IPv6 router announcements are active, a stateless DHCP IPv6 address will also be set. Further, in all network-enabled modes, at least one IPv4 or one IPv6 address will be active. •...
Viewing Network Status You can obtain the IPv6 network status through the firmware Web Interface or Command Line Interface (CLI). For the CLI, use the show network command as follows: Switched CDU: show network Network Configuration State: Static IPv4 Network: Dual IPv6/IPv4 Link: Negotiation:...
Chapter 4: Using the Web Interface This chapter shows how to work with the firmware GUI (version 8.0x or later) for the PRO2. Logging In Logging into the Web interface directs the Web client to the configured IP address of the Switched unit. To login by Web interface In the firmware login window, provide a valid username and password, and click OK.
Page 27
Working with the Pages Using a configuration page: Using the All or None global action: Switched PRO2 – User Guide • Using the Web Interface...
Page 28
Summary of the GUI Options Overview The Overview > System option is the first stop for high-level and fast monitoring of major PRO2 operational areas. The page displays a quick view of color-coded icons showing current status of the units, cords, branches, lines, phases, sensors.
Page 29
Network The Network option provides network setup options for the protocols supported by PRO2: DHCP/IP, Email/SMTP, FTP/SFTP, HTTP/HTTPS, LDAP, RADIUS, SNMP, SNTP, Syslog, TACACS+, and Telnet/SSH. The Network option only allows the administrator to set up network protocol parameters. To configure how the PRO2 user uses the network and system, see the Access option.
Overview (Viewing the System Dashboard) The System page of the Web interface is the first stop for high-level and fast monitoring of major PRO2 operational areas. The page displays a quick view of color-coded icons showing current status of the units, cords, branches, lines, phases, sensors.
Page 31
Overview > System Page Definitions The System page uses the following fields and definitions: Field Description System-assigned internal name that cannot be changed. Name User-defined descriptive name for each line or temperature/humidity sensor. Current, Temp, Current state of the reported input load (in amps), current temperature (temperature scale °C Humidity °F, as configured), or current percent of relative humidity (%RH).
Sensor Graph Color-Coding The sensor graph colors change dynamically to communicate operating conditions: For Line (Load) Status: Green = Normal Yellow = low warning/high warning (threshold configured by user) Red = low alarm/high alarm (threshold configured by user) Configure line current thresholds and threshold hysteresis at Configuration > System > Lines. For Temperature Status: Violet = coldest;...
Page 33
Sub-System Status This Sub-System section of the Summary page provides a quick status view of the current operational state of major PRO2 areas (units, cords, branches, etc.) showing a color-coded status icon. Also provided is a link from each of the sub-system areas to the related monitoring page: Click the name of one of the PRO2 system areas to display its corresponding Monitoring page.
Monitoring (Analyzing Metrics) The Monitoring section of the Web interface provides viewing of dynamically updated metrics for the PRO2 operational areas that have the highest power impact on the unit and the data center. The design of the GUI monitoring pages follows the major areas in the hardware architecture of the PRO2, providing a separate and detailed page for the overall status of units, cords, lines, OCPs, branches, outlets, groups, and sensors.
Page 35
Monitoring > Cords The Cords page displays cord hardware specifications, overall operational status of each cord, and individual color-coded graphs and status for cord active power (W), cord apparent power (VA), power factor (if present), and cord 3-phase out-of-balance level (%). Note: The inlet type, frequency, power capacity, and energy rating of the cord were determined for the PRO2 product at factory assembly and cannot be user-edited.
Page 36
Monitoring > Lines The Lines page shows overall line operational status, line load capacity, line state, and a color-coded graphic for the current used by each line. What to look for: The line status and line current status should be Normal, and the line current should be operating within defined thresholds.
Page 37
Monitoring > Phases The Phases page reports the current phase status, voltage, and power factor. What to look for: The phase status, voltage status, and phase power factor should be Normal, and the phase voltage and power factor should be operating within defined thresholds. The phase voltage graph displays a blinking warning (yellow) when the total input load on an infeed exceeds the user-defined set threshold.
Page 38
Monitoring > Over-Current Protectors The Over-Current Protectors (OCPs) page displays the current status, type, and current capacity (A) for any OCPs connected to the PRO2 unit. If there are no OCPs on the unit, the OCP monitoring page will not be available. What to look for: The operating status of all OCPs listed should be Normal.
Page 39
Monitoring > Branches The Branches page displays branch status that supports the standard Branch Current Monitoring feature of the PRO2. Branch Current Monitoring allows the configuration of thresholds on the branch circuit to provide notification before a breaker trips. Displayed on the page are branch current (A), percentage of current utilized, and threshold status.
Page 40
Monitoring > Outlets The Outlets page lists the outlets in the PRO2 unit with a quick overview of general outlet information, including operational status based on user-configured thresholds for current, active power, and power factor. Also displayed are the last user action (on, off, reboot) issued on the outlet (shown in the State column), and the outlet’s last reported condition (shown in the Control State column).
Page 41
To view details for an outlet: 1. From the Control > Outlets page, click the ID link for any outlet in the list, such as AA2 in this example. 2. The AA2 Outlet Details page displays specific information about the selected outlet that includes capacity and usage, along with status graphs for outlet current (A) and outlet power (W).
Page 42
Monitoring > Groups The Groups page shows the status of all outlets in a user-defined outlet group. An outlet group is named group with a collection of PRO2 outlets assigned to the group. The page also allows a fast drill-down by outlet ID for more details about the outlet. What to look for: The operating status of all outlets within a selected group should be Normal.
Page 43
2. When you click an outlet ID link in the list, the details page for that outlet displays: 3. The AA14 Outlet Details page displays specific information about the selected outlet that includes capacity and usage, along with status graphs for outlet current (A) and outlet power (W). 4.
Page 44
Monitoring > Sensors The Sensors page provides a quick view of the operating status and color-coded graphic showing current operating value of environmental sensors for temperature and humidity. What to look for: The operating status of all sensors should be Normal, and operating temperature or relative humidity should be within defined thresholds.
Page 45
Temperature/Humidity Sensor Status Status Description Found The PRO2 found the sensor and connection is established. Not Found On a fresh reboot, the PRO2 does not find a sensor. Lost The connection to a previously found sensor is now lost. No Comm Communication loss occurred due to a hardware issue (not loss of communication with the probes).
Page 46
Environmental Monitor (EMCU) Status If an EMCU is connected to the PRO2, the Sensors pages will also include monitoring of water, contact closures, and analog-to-digital (ADC) sensors. What to look for: The operating status of all sensors should be Normal and operating within defined thresholds. View the color-coded graph showing current operating range within thresholds for the ADC.
Page 47
Monitoring > UPS The UPS page identifies each UPS device connected to the PRO2 unit, displaying hostname/IP address and UPS status. What to look for: Monitoring page will be blank if a UPS has not been connected to, and configured for, the PRO2. After connecting a UPS to the unit, configure the UPS and the lines to be powered by the UPS at Configuration >...
Control (Managing Outlets) The Control section of the Web interface allows the issuing of outlet control actions On, Off, and Reboot for individual outlets in a master unit (or in all units), for all outlets globally in a master unit (or in all units), and for named outlet groups.
Page 49
To view detailed operational details for an outlet: 1. From the Outlet Control page, click the Outlet ID link for any outlet in the list, such as AA2 in this example. 2. The Outlet Details page displays for outlet AA2 showing power, capacity, and other operational information: Switched PRO2 –...
Page 50
Control > Groups The Control Groups page displays outlet groups assigned to a current user and allows power control actions (On, Off, Reboot) to be applied to all outlets in a selected outlet group. Note: An outlet group is a named collection of outlets in a PRO2 (up to four enclosures) with a single IP address.
Page 51
Outlet State/Control State Descriptions The following table shows the differences between outlet state and control state The outlet state is the current operating state of the outlet. • The control state is the last user-issued control action on the outlet. •...
Configuration (Setting Values) The Configuration section allows administrative access to all options for setting PRO2 values. The pages are organized into three major areas of configuration: System (options for PRO2 hardware areas) • Network (options for setting up network protocols) •...
Page 53
• The ST Eye mobile app and the Bluetooth module may not be included with the PRO2. • The ST Eye mobile app supports one concurrent session. • Learn more about the Bluetooth monitoring solution (for either Android or iOS) at Server Technology’s Technical Notes page http://www.servertech.com/support/technical_library/technical_notes/...
Page 54
System > Branches The Branches page provides the Branch Current Monitoring feature of the PRO2 to support up to six branches to measure, report, and alert (in Amps) per branch circuit for breaker and fuse errors. The Branches pages allows setting multiple load levels for low/high warning/alarm values (A) for branch current thresholds, plus threshold hysteresis (A).
Page 55
Setting Branch Current Thresholds From the Branches page, click the link Branch Current Thresholds to display the related thresholds edit page: To set branch current thresholds: 1. Set the threshold hysteresis value (in Amps). Hysteresis is the values between the event state and recovery.
Page 56
System > Cords The Cords page configures the single input power cord in the PRO2 hardware architecture that reports infeed data for the unit, allowing the setting of multiple cord threshold levels for power, apparent power, power factor, 3-phase out-of-balance, and threshold hysteresis. The value for nominal voltage –...
Page 57
Configuring Cord Power Thresholds Click the power thresholds link at the bottom of the Cords page to display the configuration page: To set power thresholds: 1. Provide the threshold hysteresis between event state and recovery (W). Range is 0-1000W; default is 100W.
Page 58
To set apparent power thresholds: 1. Provide the threshold hysteresis between event state and recovery (VA). Range is 0-1000VA; default is 100VA. 2. Set the low/high alarm and low/high warning threshold values (VA). Cord apparent power includes power factor. Range is min 0VA; max is power capacity shown in cstat command. 3.
Page 59
Configuring 3-Phase Out-Of-Balance Thresholds Click the out-of-balance link at the bottom of the Cords page to display the configuration page: To set out-of-balance factor thresholds: 1. Provide a percent for threshold hysteresis between event state and recovery. Range is 0-10%; default is 2.
Page 60
System > Features The Features page allows the activation of add-on features available from Server Technology. To activate a feature: 1. In the Feature Key field, type the key provided by Server Technology. 2. Click Apply. A restart of the PRO2 is required after activating a feature.
System > Files The Files page provides a separate embedded file system to give quick access to system configuration files directly from the PRO2 GUI page, as well as the on-board and downloadable Sentry4-MIB and OID Tree for the PRO2, eliminating website MIB/OID downloads.
Page 62
The PRO2 is configured to recognize and use the configuration values in the file as specified by the network administrator, indicating to the RADIUS server that the defined attributes are based on Server Technology’s unique enterprise vendor code. For more information about the dictionary file and RADIUS, see...
Page 63
The Sentry4-MIB and OID tree for the PRO2 can be accessed on-board in the GUI via Configuration > System > Files, or accessed by using the Server Technology FTP site the same way as with the Sentry3-MIB and OID tree for the earlier PDU products.
Page 64
sentry4OIDTree.txt The Sentry4OIDTree is the new OID tree structure that identifies PRO2 data objects for SNMP network monitoring. The Sentry4OIDTree is not backward-compatible with the Sentry3OIDTree. Continue to use the Sentry3OIDTree for SNMP network monitoring of PDU products, and use the Sentry4OIDTree exclusively for PRO2 products.
Page 65
System > Groups The Groups page lets the administrator create and name a new outlet group and assign to the group access rights to individual (or all) outlets. For dynamic monitoring of outlets assigned to a group, see the separate Monitoring > Groups page.
Page 66
To grant individual outlet access rights to an outlet group: 1. For the group name displayed in the list, click the Access link. The Group Access page displays to allow granting access rights to individual outlets by checking corresponding outlet checkboxes (or unchecking a checkbox to deny rights).
System > Lines The Lines page configures the separate area of the PRO2 cord architecture that reports current line load, allowing the setting of multiple line threshold levels, plus threshold hysteresis. The page also sets SNMP Trap and Email notifications for line events. For dynamic monitoring of line status and current, see the separate Monitoring >...
Page 68
Configuring Line Current Thresholds Click the thresholds link at the bottom of the Lines page to display the configuration page: To set line current thresholds: 1. Provide the threshold hysteresis between event state and recovery (A). Range is 0.0-10.0A; default is 1.0A. 2.
Page 69
System > Outlets The Outlets page allows configuration of global outlet parameters and outlet shutdown options, including the setting of multiple threshold levels for outlet current, outlet power, and outlet power factor, plus the threshold hysteresis. The page also sets sets SNMP Trap and Email notifications for outlet events. For outlet management: the issuing of On, Off, and Reboot commands on individual outlets and all outlets globally, see the separate Control >...
Page 70
5. View the reported type of socket displayed for the outlet. 6. In the Extra On Delay field, for a specific outlet, set the value (in seconds) for an extra delay when turning on the outlet. Range is 0-900 seconds. 7.
Page 71
Configuring Outlet Power Thresholds Click the outlet power thresholds link at the bottom of the Outlets page to display the configuration page: To set outlet power thresholds: 1. Provide the threshold hysteresis between event state and recovery (W). Range is 0-1000W; default is 10W. 2.
Page 72
Configuring Outlet Power Factor Thresholds Click the outlet power factor thresholds link at the bottom of the Outlets page to display the configuration page: To set outlet power factor thresholds: 1. Provide a numeric value for the threshold hysteresis between event state and recovery. Range is 0.0-0.20; default is 0.02.
Page 73
System > Over-Current Protectors (OCPs) The Over-Current Protectors page configures current load settings for each OCP connected to the PRO2 unit as a standard and separate area of the PRO2 architecture. The page also sets sets SNMP Trap and Email notifications for OCP events.
Page 74
System > Phases The Phases page configures multiple threshold levels for phase voltage and power factor, plus threshold hysteresis (for AC products only). The page also sets sets SNMP Trap and Email notifications for phase events. For dynamic monitoring of phase status, voltage, and power factor, see the separate Monitoring > Phases page. To set phase event notifications: 1.
Page 75
Configuring Phase Voltage Thresholds Click the phase voltage thresholds link at the bottom of the Phases page to display the configuration page: To set phase voltage power thresholds: 1. Provide the threshold hysteresis between event state and recovery (V). Range is 0.0-20.0V; default is 2.0V. 2.
Page 76
Configuring Phase Power Factor Thresholds Click the phase power factor thresholds link at the bottom of the Phases page to display the configuration page: To set phase power factor thresholds: 1. Provide a numeric value for the threshold hysteresis between event state and recovery. Range is 0-0.20; default is 0.02.
Page 77
System > Ports The Ports page configures options for the external serial port on the PRO2 unit. To configure the serial port: 1. From the Baud Rate drop-down menu, select the data rate. 2. Set the Timeout value (in minutes) for the serial port inactivity timeout period. The timeout period defines the maximum period of inactivity before automatically closing the pass-thru session.
Page 78
System > Sensors The Sensors page configures multiple threshold levels for global temperature sensors and relative humidity sensors, plus threshold hysteresis. The page also determines the system-wide temperature scale and sets SNMP Trap and Email notifications for sensor events. For dynamic monitoring of sensor temperature/humidity and operational status, see the separate Monitoring > Sensors page.
Page 79
Configuring Humidity Sensors Thresholds Click the humidity sensor thresholds link at the bottom of the Sensors page to display the configuration page: To set humidity sensor thresholds: 1. Provide the threshold hysteresis between event state and recovery(%RH). Range is 0-20%RH; default is 2%RH.
Page 80
Configuring Temperature Sensors Thresholds Click the temperature sensor thresholds link at the bottom of the Sensors page to display the configuration page: To set temperature sensor thresholds: 1. Provide the threshold hysteresis between event state and recovery temperature. Range is 0-30° Celsius, or 0-54°...
Page 81
Configuring Environmental Monitoring (EMCU) Thresholds If an EMCU is connected to the PRO2 unit, the Sensors page will also allow configuration of water, contact closure and analog-to-digital (ADC) voltage sensors – to provide sensor name and SNMP/Email notifications. In addition, for ADC voltage sensors only, high/low warning/alarm thresholds can be set. Water and contact closure sensors can have either Normal or Alarm status –...
Page 82
System > Shutdown The Shutdown page configures the remote shutdown options for outlets (for Switched PRO2 products only). The PRO2 supports the ability to initiate an orderly shutdown of a specific outlet or outlet group after performing a user-specified shutdown operation. The shutdown also protects open application files prior to a server being powered down.
Page 83
Shutdown and Smart Load Shedding The Smart Load Shedding feature allows the load shedding of outlet loads, both on CDU and PRO2 products, based on UPS condition (on-battery), temperature level, and input current load. The Shutdown feature for Switched products is also supported by the extended license-key feature Smart Load Shedding.
Page 84
System > Trending The Trending page generates a report (and related source data sets) of measured system trends over a 7-day period, with the range of each day from midnight to midnight. The trend data in the report is for viewing and analysis only –...
Page 85
What Data Does Trending Measure? REQUIREMENTS For the Trending feature to occur and display (for viewing only) on the PRO2 GUI at System > Trending, SNTP must be enabled to keep track of when daily measurements are taken. Certain measurements for PIPS and POPS (if POPS is present) are tracked by the Trending feature: For all PIPS cords/phases/lines, the following measurements are tracked: Phase voltage •...
Page 86
How Does the Trending Feature Work? Each time a measurement is taken on the PRO2 unit, the measurement is aggregated into the metrics for the current day. The aggregation process includes updating the maximum and minimum values for each measurement, as well as updating the average with the new measurement.
Page 87
About the Trending Report The report (and the data sets the report is generated from) are all stored separately. • The report is created at midnight. • • The report contains the percent change of the average, maximum, and minimum measurements of the day compared to the daily metrics from the same day on the previous week (7 days ago).
Page 88
System > Units The Units page sets a descriptive system name for each PRO2 unit, configures asset management identification, determines outlet sequence, and sets the display orientation of the mounted unit. The page also sets sets SNMP Trap and Email notifications for unit events. The Purge and Restore link on the Units page displays another page to allow the clearing of current values in non- volatile (NV) memory from individual units, and the resetting of those values back to factory defaults.
Page 89
Set Unit Defaults – System Settings Unchanged The Set Unit Defaults – System Settings Unchanged function resets the following subset of configuration items (in the NIC of the master PRO2 unit) to factory default values: • Power items: Cords, lines, phases, over-current protectors (OCPs), branches, outlets. •...
Page 90
System > UPS The UPS page manages UPS devices connected to a PRO2 unit. A connected UPS device can be added to or deleted from the system. Several device options are available for configuration, including a configurable UPS name, and assignment of PRO2 lines to be powered by the UPS. To add a new UPS: 1.
Page 91
Configuring a UPS: For a UPS listed on the page, click the Edit link to display the edit window: To configure a UPS: 1. From the Type drop-down list, select the UPS manufacturer. 2. Type the desired values for the SNMP-related fields or accept the defaults as shown on the page. 3.
Network (Setting Up Network Protocols) The Network section of the Web interface provides network setup options for the protocols supported by PRO2: DHCP/IP, Email/SMTP, FTP, HTTP/HTTPS, LDAP, RADIUS, SNMP, SNTP, Syslog, TACACS+, and Telnet/SSH. Note: The Network section only allows the administrator to set up network protocol parameters. To configure how the PRO2 user uses the network and system, see the Access section.
Page 93
To configure static IPv4/IPv6: 1. IPv4/IPv6 Address/Gateway: Provide the address for these fields in either IPv4 or IPv6 format. 2. IPv4 Subnet Mask: If IPv4 is used, supply the IP address for the subnet mask in IPv4 format. 3. Primary/Secondary DNS: Provide the IP address for the primary and secondary DNS hostnames. To configure DHCP settings: 1.
Page 94
Network Defaults The PRO2 has the following network defaults to allow unit configuration through Telnet or Web: IP Address: 192.168.1.254 Subnet Mask: 255.255.255.0 Gateway: 192.168.1.1 The initial local PC network connection must be configured as follows: IP Address: 192.168.1.x (where x is 2-253). Subnet Mask: 255.255.255.0 Note: The PRO2 must be restarted after network configuration changes.
Page 95
Network > Email/SMTP The Email/SMTP page allows configuration of the Email/SMTP protocol and email options. Authentication Notes: • SMTP authentication allows the mail client in the PRO2 to log into the mail server during the process of sending an email. The mail server may require this login to relay mail to another mail server.
Page 96
To configure Email notification options: 1. Check the Enable checkbox to enable Email notifications to be sent. 2. For the event notifications shown, check the corresponding Enable checkbox to enable an alert message via email. The events are: EVENT: System activity event AUTH: Authentication event POWER: Power event CONFIG: System configuration event...
Page 97
Network > FTP The FTP configuration page allows configuring the settings required for the FTP client to perform FTP firmware uploads and automatic system uploads/downloads. To configure FTP client options: 1. Type the hostname/IP addresses in the Host field (IPv4 or IPv6 format). 2.
Page 98
Network > HTTP/HTTPS The HTTP/HTTPS page configures server options for HTTP, HTTPS, and SSL, including user-defined certificates. The page also determines settings for the Sentry Power Manager (SPM) enterprise software product. To configure HTTP and HTTPS/SSL: 1. Server: Check (or uncheck) the Enable checkboxes to enable/disable support for the HTTP and/or HTTPS/SSL server options.
Page 99
4. Installed Certificate: Shows the type of certificate that was installed – Factory, User, Company. To configure Sentry Power Manager (SPM) options: The Sentry Power Manager (SPM) is Server Technology’s enterprise management software product for the data center. The configuration options provided allow you to enable/disable SPM and reset the SPM password to its default.
Page 100
Network > LDAP The LDAP page determines the protocol settings required to enable LDAP support. Note: The Network > LDAP page is for LDAP network protocol management only. To manage LDAP user groups, see the Access > LDAP Groups page. The Change Access Configuration link takes you to the Access page to determine user access method for LDAP.
Page 101
11. Base DN: Indicates where the LDAP group search will start. 12. User Membership Attribute: The user membership option allows the searching of directory entries of groups for a user membership attribute to find the groups for which the user is a member. Provide a comma- delimited string of up to two attribute names whose values in the search results are the users that are members of the group.
Page 102
Server Technology has defined and formatted RADIUS vendor-specific attributes (VSA) in the dictionary.sti file, which is available from Server Technology. The PRO2 is configured to recognize and use the configuration values in the file as specified by the network administrator, indicating to the RADIUS server that the defined attributes are based on Server Technology’s unique enterprise vendor code.
View-Only user with environmental monitoring allowed and all outlet and group access rights: sti-view Auth-Type := Local, User-Password == "view" STI-Access-Level = View-Only, STI-Env-Mon = Yes, STI-Outlets = "ALL", STI-Outlets = “ALL” Network > SNMP The SNMP page provides the protocol and agent configuration options for SNMP support. About SNMP Versions The firmware supports SNMP v1, v2c, and v3.
Page 104
3. SET community (RW): Community strings for SET commands. 4. Click Apply. Note: The default for SNMP support is Enabled. When Server Technology products are shipped, the default SNMP configuration for the GET community string is set to “public” and the SET community string is left blank.
Page 105
Network > SNTP The SNTP page provides configuration options for the SNTP server, time zone, and Daylight Saving Time (DST) automatic clock adjustment. About Daylight Saving Time (DST) Support for DST is enabled by default. When enabled, the date and time are automatically adjusted forward one hour between the starting and ending dates/times, which can be configured.
Page 106
To configure the SNTP server: 1. Local Date/Time: Displayed to show the local and current DST settings. To increment the settings (based on updates to the options for DST Start/DST End and day/time), click the Update link. 2. The Primary/Secondary Host fields contact the SNTP server. The fields are populated with the the external NTP pool time zones “2.servertech.pool.ntp.org”...
Page 107
Network > TACACS+ The TACACS+ page allows configuration for TACACS+ server options, encryption key, and user privilege levels. The Change Access Configuration link takes you to the Access page to determine user access method for TACACS+. Click link to configure privilege levels. To configure TACACS+ server options: 1.
Page 108
Assigning User Access Rights to TACACS+ Privilege Levels 1. At the bottom of the TACACS+ screen, click the TACACS+ Privilege Levels link to display the following edit page which shows the current user access level for each TACACS+ privilege level. Privilege level 15 is assigned by default for administrator access rights to all PDU resources.
Page 109
Configuring TACACS+ Privilege Levels The PRO2 supports 16 different TACACS+ privilege levels. The administrative-level user can configure 15 privilege levels. One level is reserved by default for access to all PRO2 resources by the administrative-level user. Six defined user privilege levels are available: Admin, Power User, User, On-Only User, Reboot-Only User, and View- Only User.
Page 110
3. From the Access Level drop-down menu, select a user access level for the displayed TACACS+ privilege level, as described: User Access Level Description (highest to lowest) Administrator Administrative user; full access for all configuration, all outlet power control actions (On, Off, Reboot), status, and serial/pass-thru ports.
Page 111
Network > Telnet/SSH The Telnet/SSH page provides server, port, and authentication options for support of Telnet and SSH. To configure the Telnet server and/or SSH server: 1. Server: Check (or uncheck) the Enable checkbox to enable/disable support for Telnet and/or SSH. 2.
Page 112
For more information about setting network configurations for the wireless network, a description of the PRO2 products designated for this solution, and considerations for access point (AP) installation, see Server Technology’s website, www.servertech.com, for Technical Note, 303-9999-37, “Wi-Fi Solution with 802.11b/g/n Support for Wi-Fi Capable PRO2 Products.”...
Access (Managing Users) The Access section of the Web interface determines how a PRO2 user works with the network and system by configuring the options related to a user: authentication, privilege levels, user access to the unit, and additional functions for individual local users and user groups. Note: The Access section only allows the administrator to determine how the PRO2 user uses the network and system.
Page 114
3. Local Administrator Account: Removes the last local administrator account when remote authentication (LDAP, TACACS+, or RADIUS) is in use. Only a remotely-authenicated administrator can remove the last local administrator account. Accept the “Required” option (default), or select “Optional”. Selecting “Optional” disables the restriction to remove the last local administrator, and also enables the Configuration Reset Button.
Login Banner: Clicking the Login Banner link displays a blank banner edit window. The following example shows a custom message: The Characters Remaining box shows as you type (in real time) how many of the 2070 maximum characters are still available to complete the banner.
Page 116
Access > Local Users The Local Users page allows the administrator to manage options for local users, including creating new users, changing user passwords, setting user access level, and granting user access to various resources of the PRO2. To create a new local user: 1.
Page 117
To set a user’s access level: 1. For the user name displayed in the list, click the Edit link. The Local User Edit page displays. 2. From the Access Level drop-down menu, select the desired user access level as described in the table below.
Page 118
Access > LDAP Groups The LDAP Groups page allows the administrator to manage options for LDAP user groups, including creating new LDAP groups, establishing the LDAP group access level, and granting LDAP group access to various resources of the PRO2. The LDAP Groups page is for LDAP group management only.
Page 119
To set an LDAP group’s access level: 1. For the LDAP group name displayed in the list, click the Edit link. The LDAP Group Edit page displays. 2. From the Access Level drop-down menu, select the desired user access level as described in the table below.
Page 120
Access > TACACS+ Privileges The TACACS+ Privileges page allows the administrator to manage options for TACACS+ user groups, including establishing TACACS+ privilege levels and granting TACACS+ privilege level access to various areas of the PRO2. Note: The PRO2 supports 16 different TACACS+ privilege levels with 15 configurable levels and 1 level (“0”) reserved by default for administrator-level access to all PRO2 resources.
Page 121
To grant access rights to a TACACS+ privilege level: 1. For the TACACS+ Privilege Level displayed in the list, click the Access link. The TACACS+ Privilege Level Access page displays to allow granting access rights to selected PRO2 monitors, remote ports, outlet groups, and individual outlets by checking corresponding checkboxes.
Tools (Using Support Functions) The Tools section of the Web interface is a collection of several utility options for miscellaneous system actions: changing user password, pinging other network devices, viewing the system/debug log, and uploading new firmware versions. Also included are several options for rebooting the PRO2, resetting the PRO2 to factory defaults, and restarting the PRO2 with user preferences.
Page 123
Tools > Ping The Ping option tests the ability of the PRO2 to contact the IP address of another Ethernet-enabled device. For LDAP support, the Ping feature can test the configuration of the DNS IP address by testing for proper name resolution. To issue a ping: 1.
Page 124
Tools > Restart The Restart option offers several options for restarting the PRO2. To initiate a system restart: 1. From the Action drop-down menu, select a restart option as described in the table below. 2. Click Apply. Switched PRO2 – User Guide •...
Page 125
Restart Options for the PRO2: Note: PRO2 products support unit persistence. This means that if a link unit is connected to a master unit, and the link unit is disconnected (powered down or accidentally disconnected), and the master unit is restarted, the link unit will be reported as “Not Found”...
Page 126
About the Reset Button on the PRO2 Unit: The PRO2 is designed with a Reset button on the hardware unit that can be used when a forgotten firmware password prevents logging into the unit. The Reset button sets all configuration values back to factory default settings, allowing the administrator to retrieve the admn/admn default administrator login.
Page 127
This example shows the filtered results of the system log (highlighted in the example) filtered by “BA:L1”. Browse the system (or debug) log by using the page navigation links at the top and bottom of the log. To sort system log entries: The entries in the System/Debug Log can be displayed in ascending or descending order (based on the internal index number in the Index column) by clicking one of the following icons: For ascending order, click...
Page 128
System log status icons: Normal Configuration Change Low/High Warning Low/High Alarm Options for Log Viewing Viewing options for the System Log are set on the Configuration > Access page: Web Log Entries Per Page: Specifies the number of entries displayed on the System Log and the Debug •...
Page 129
The Debug Log Along with the System Log, the Debug Log is also provided. The Change link on each log toggles between logs, as illustrated in the following two examples: Click the Change link from the System Log (above) to display the following Debug Log: The icons, fields and information columns shown on the Debug Log function the same way as described for the System Log with the following exceptions: •...
Chapter 5: Using the Command Line Interface (CLI) This chapter shows how to work with the firmware CLI (version 8.0x or later) for the PRO2. Logging In Logging in through Telnet requires directing the Telnet client to the configured IP address of the unit. A login through the console (RS232) port requires the use of a terminal or terminal emulation software configured to support ANSI or VT100, and a supported data rate of 300, 1200, 2400, 4800, 9699, 19200, 38400, 57600, or 115200 bps (default rate is 9600);...
Page 131
Using CTRL-C to Cancel Commands CLI command operations can be cancelled by using the keys CTRL-C, where applicable. Editing Commands Several editing actions are available when typing a command: This edit action… does this on the command line… Left Arrow Moves cursor to the left to correct a typed character.
Page 132
Displaying the Submenus To view submenus of valid options for a command, type the main command and press Enter: Example: Switched CDU: set 'set' menu options: access banner bluetooth branch config cord dhcp email energywise feature http https ipv4 ipv6 ldap ldapgroup line...
List of Commands Click a linked command name in the following table to display detailed information about using the command. Command Description Add Commands The Add command group adds control access for outlets/outlet groups, and connection pass-thru to specified ports for LDAP, TACACS+, and local users. add grouptoldap Adds control access for an outlet group to an LDAP group.
Page 134
Command Description delete outletfromldap Deletes control access for an outlet from an LDAP group. delete outletfromtacacs Deletes control access for an outlet from a TACACS+ privilege level. delete outletfromuser Deletes control access for an outlet from a local user. delete portfromldap Deletes access to use a connection pass-thru to a specified port from an LDAP group delete portfromtacacs Deletes access to use a connection pass-thru to a specified port from a TACACS+ privilege...
Page 135
Command Description Turns on the specified outlet or outlet group. ostat Displays the latest status and metrics for all outlets in the system. password Changes the password for the current local user. ping Tests the ability of the PRO2 to contact an IP address for another Ethernet-enabled device. pstat Displays the latest status and metrics for all phases in the system.
Page 136
Command Description set https Sets HTTPS configuration values. set ipv4, set ipv6 Sets IPv4 and IPv6 configuration values. set ldap Sets LDAP configuration values. set ldapgroup Sets configuration values for LDAP group access rights. set line Sets line configuration values. set loadshed Sets Smart Load Shedding configuration values.
Page 137
Command Description set user Sets configuration values for local user access rights. set wlan Sets the wireless network configuration (for the WLAN solution on specific Wi-Fi capable PRO2 units). Show Commands The Show command group displays the current configuration values in the system. show access Shows user access configuration values.
Page 138
Command Description show syslog Shows Syslog configuration values. show system Shows system uptime, firmware version, firmware build information, boot version, number of active users, and location string. show tacacs Shows TACACS+ configuration values. show trend Shows power trending configurations. show units Shows PRO2 configuration values.
Command Details add grouptoldap Adds control access for an outlet group to an LDAP group. Command Syntax add grouptoldap <group name | ALL> <LDAP group name> add gtl <group name | ALL> <LDAP group name> Command Access Admin level only add grouptotacacs Adds control access for an outlet group to an TACACS+ privilege level.
Page 140
add outlettoldap Adds control access for an outlet to an LDAP group. Command Syntax add outlettoldap <outlet name | id | ALL> <LDAP group name> add otl <outlet name | id | ALL> <LDAP group name> Command Access Admin level only add outlettotacacs Adds control access for an outlet to a TACACS+ privilege level.
Page 141
add porttotacacs Adds access to use a connection pass-thru to a specified port to a TACACS+ privilege level. Command Syntax add porttotacacs <port name | id | ALL> <TACACS+ privilege level> add ptt <port name | id | ALL> <TACACS+ privilege level> Command Access Admin level only add porttouser...
Page 142
create group Creates a new outlet group. Command Syntax create group <name> Command Access Admin level only create ldapgroup Creates a new LDAP group. Command Syntax create ldapgroup <name> Command Access Admin level only create ups Creates a new uninterruptable power supply (UPS). Command Syntax create ups <name | ups type |>...
Page 143
delete groupfromldap Deletes control access for an outlet group from an LDAP group. Command Syntax delete groupfromldap <group name | ALL> <LDAP group name> delete gfl <group name | ALL> <LDAP group name> Command Access Admin level only delete groupfromtacacs Deletes control access for an outlet group from a TACACS+ privilege level.
Page 144
delete outletfromtacacs Deletes control access for an outlet from a TACACS+ privilege level. Command Syntax delete outletfromtacacs <outlet name | id | ALL> <TACACS+ privilege level> delete oft <outlet name | id | ALL> <TACACS+ privilege level> Command Access Admin level only delete outletfromuser Deletes control access for an outlet from a local user.
Page 145
delete portfromuser Deletes access to use a connection pass-thru to a specified port to a local user. Command Syntax delete portfromuser <port name | id | ALL> <local user name> delete pfu <port name | id | ALL> <local user name> Command Access Admin level only (Directory) Displays the contents of the active working path in the file system.
list ldapgroup Lists access level of an LDAP group and any outlet groups, outlets, and ports assigned to that LDAP group. Command Syntax list ldapgroup <LDAP group name> Command Access Admin level only list ldapgroups Lists all LDAP groups. Command Syntax list ldapgroups Command Access Admin level only...
list tacprivs Lists all TACACS+ privilege levels. Command Syntax list tacprivs Command Access Admin level only list user Lists access level of a local user and any outlet groups, outlets, and ports assigned to that user. Command Syntax list user <username> Command Access Admin level only list users...
Page 148
logout Quits the current CLI session. Command Syntax logout Command Access Any access level lstat Displays the latest status and metrics for all lines in the system. Command Syntax lstat Command Access System monitor access ocpstat Displays the latest status and metrics for all over-current protectors (OCPs) in the system. Command Syntax ocpstat Command Access...
Page 149
Turns on the specified outlet or outlet group. Command Syntax on <name | id | group | ALL> Usage Guidelines The on command is for Switched PRO2 products only. Command Access On-Only users or User level and above ostat Displays the latest status and metrics for all outlets in the system. Command Syntax ostat <name | outlet | outlet id | group | ALL>...
pstat Displays the latest status and metrics for all phases in the system. Command Syntax pstat Command Access System monitor access reboot Turns off the specified outlet or outlet group and then turns it back on after a delay. Command Syntax reboot <name | id | group | ALL>...
remove user Removes a local user from the system. Command Syntax remove ups <name> Command Access Admin level only restart Restarts the system. Command Syntax restart [factkeepnet | factory | ftpload | newx509cert | newsshkeys | normal] Parameters The restart command uses the following parameters. Note: None of the parameters in the following table performs a normal system restart.
Command Access Admin level only set banner Sets the system banner that displays before a user authenticates a user session. Command Syntax set banner <banner text> Parameters The set banner command uses the following sub-parameters: banner text Text for system banner, 0-2070 characters. Usage Guidelines •...
Page 154
set branch Sets branch configuration values. Command Syntax set branch email [disabled | enabled] <name | id | ALL> set branch load [alarmhi | alarmlo | warnhi | warnlow] <name | id | ALL> <value> set branch load hyst <value> set branch snmpt [disabled | enabled] <name | id | ALL>...
Page 155
set cord Sets cord configuration values. Command Syntax set cord email [disabled | enabled] <name | id | ALL> set cord loadmax <name | id | ALL> <value> set cord name <name | id> <name string> set cord nomvolts <name | id | ALL> <value> set cord outofbal [alarmhi | warnhi] <name | id | ALL>...
Page 156
set dhcp Sets DHCP configuration values. Command Syntax set dhcp [disabled | enabled] set dhcp fqdn [disabled | enabled] set dhcp fqdn name <name> set dhcp staticfallback [disabled | enabled] set dhcp bootdelay [disabled | enabled] Parameters The set dhcp command uses the following parameters: fqdn Fully-qualified domain name (FQDN).
set email Sets email configuration values. Command Syntax set email auth [disabled | enabled] set email config [disabled | enabled] set email [disabled | enabled] set email event [disabled | enabled] set email fromaddr <email addr> set email power [disabled | enabled] See Note below.
Page 158
userfromaddr Sets to log into the relay SMTP server using the from address. username Sets the username for logging into the relay SMTP server. 0-32 characters, spaces are not allowed. test Tests the email setting for logging into the relay SMTP. usesubjloc Uses the location string as the subject of the relayed emails.
Page 159
set feature Enables new system features. Command Syntax set feature <feature key> Parameters The set feature command uses the following parameter: feature key Key for unlocking system features (XXXX-XXXX-XXXX-XXXX), where X = 0-9 or A-Z. Command Access Admin level only set ftp Sets FTP configuration values.
Page 160
Sub-Parameters The set ftp command uses the following sub-parameters: Sets the day of the week to automatically update system firmware. hour Sets the hour of the day to automatically update system firmware. Command Access Admin level only; no access in Demo mode set http Sets HTTP configuration values.
Page 161
set ipv4, set ipv6 Sets IPv4 and IPv6 configuration values. Command Syntax set ipv4 address <ipv4 address> set ipv4 gateway <ipv4 address> set ipv4 subnet <ipv4 address> set ipv6 address <ipv6 address> set ipv6 gateway <ipv6 address> set ipv6 prefix <ipv6 CIDR prefix> Parameters The set ipv4 and set ipv6 commands use the following parameters: Ipv4 address...
Page 162
hostname Sets the hostname of the Directory Services server. port Sets the port number for the LDAP server. 1-65535 (default 389). userbasedn Sets the base distinguished name (DN) for the username search at login. userfilter Sets the filter used for the username search at login. Sub-Parameters The set ldap command uses the following sub-parameters: simple...
Page 163
set line Sets line configuration values. Command Syntax set line email [disabled | enabled] <name | id | ALL> set line load [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value> set line load hyst <value> set line snmpt [disabled | enabled] <name | id | ALL>...
Parameters The set loadshed command uses the following parameters: branch Sets to allow branch shedding events. line Sets to allow line shedding events. sensor Sets to allows sensor shedding events. Sets to allow UPS shedding events. Sub-Parameters The set loadshed command uses the following sub-parameters: Sheds outlets only when all UP devices on an upstream line go to “on battery”.
Page 165
set net Sets network mode configuration values. Command Syntax set net [disabled | ipv4only | dualv6v4] Parameters The set net command uses the following parameters: disabled Disables network access to system. ipv4only System only allows IPv4 functionality. Dualv6v4 System allows IPv6 and IPv4 functionality. Command Access Admin level only;...
Page 166
set outlet Sets outlet configuration values. Command Syntax set outlet branchevent [disabled | enabled] <name | id | ALL> set outlet chglogging [disabled | enabled] set outlet email [disabled | enabled] <name | id | ALL> set outlet load [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value> set outlet load hyst <value>...
Page 167
extondelay Sets an extra on delay when turning on an outlet. 0-900 seconds. Sets the hostname for an outlet for script or shutdown actions. host 0-63 characters. hyst Sets the hysteresis between event state and recovery. load Sets the current load for an outlet. min 0.0A, max (max current) in show outlets command, hyst 1.0-10.0A (default 1.0A) lineevent Sets if load shedding (due to outlet current load events) is allowed for...
Page 168
Parameters The set outlet command uses the following sub-parameters: script delay Sets the time to wait after the script has executed to outlet state change. 1-15 seconds. Sets the time to wait after the shutdown notification to host before outlet shutdown delay state change.
Parameters The set port command uses the following parameters: baud/speed Sets the number of symbols per second of the serial port. dsrcheck Sets to use DSR before making a serial connection. timeout Sets the connection idle timeout for pass-thru connections to this port. 0-60 minutes (default 5 minutes).
Page 171
set sensor Sets sensor configuration values. Command Syntax set sensor adc [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value> set sensor adc email [disabled | enabled] <name | id | ALL> set sensor adc hyst <value> set sensor adc name <name | id>...
Page 172
Sub-Parameters The set sensor command uses the following sub-parameters: alarmhi Sets high alarm value. alarmlo Sets low alarm value. warnhi Sets high warning value. warnlo Sets low warning value. min <= alarmlo <= warnlo <= warnhi <= alarmhi <= max Command Access Admin level only set snmp...
Page 173
Sub-Parameters The set snmp command uses the following sub-parameters: dest1 First SNMP trap destination. 0-63 characters. dest2 Second SNMP trap destination. 0-63 characters. format Format of SNMP trap and header. repeat Sets the SNMP trap repeat time for object in an event condition. 1- 65535 seconds.
Page 174
set sntp Sets SNTP configuration values. Command Syntax set sntp dst [disabled | enabled] set sntp dst [end | start] <tz string> set sntp gmtoffset <offset> set sntp primary <hostname> set sntp secondary <hostname> Parameters The set sntp command uses the following parameters: Sets to automatically adjust for Daylight Saving Time (DST).
set ssh Sets SSH configuration values. Command Syntax set ssh [disabled | enabled] set ssh port set ssh authmethod [all | kbint | password] Parameters The set ssh command uses the following parameters: port Sets port for SSH connections 1-65535 (default is 22). authmethod Sets authentication method for SSH connections.
Page 176
set tacacs Sets TACACS+ server configuration values. Command Syntax set tacacs primary <hostname> set tacacs secondary <hostname> set tacacs port <port> set tacacs key {key} Parameters The set tacacs command uses the following parameters: primary Sets the first TACACS+ server (0-63 characters). secondary Sets the second TACACS+ server (0-63 characters).
set telnet Sets Telnet configuration values. Command Syntax set telnet [disabled | enabled] set telnet port <port> Parameters The set telnet command uses the following parameters: port Sets the port for Telnet connections 1-65535 (default is 23). Command Access Admin level only; no access in Demo mode set trend Sets power trending configurations.
Page 178
identify Set to enable/disable flashing display. name The name of the unit. 0-32 characters. osequence Sets the outlet sequence order for a unit. prodsn Sets the product serial number for a unit. 0-32 characters. purge Removes all stored information for a unit. snmpt SNMP trap notifications for unit events.
Page 179
oidspoll The OID for getting the “on battery”/“on utility” value when polling the UPS by SNMP. onbattery Value of the OID when the UPS is in an “on battery” state. 1-65535. onutility Value of the OID when the UPS is in an “on utility” state. 1-65535. port Port number for polling the UPS by SNMP.
set wlan Description : Sets the wireless network configuration. Command Syntax: set wlan [disabled | enabled] set wlan bssid <ap bssid> set wlan key <ap key> set wlan mac <mac address> set wlan security [open | wep-open | wep-shared | wpapsk-aes | wpapsk-tkip | wpapsk-tkipaes | wpa2psk-aes | wpa2psk-tkip | wpa2psk-tkipaes] set wlan ssid <ap ssid>...
Page 181
show bluetooth Shows Bluetooth ® configuration values. Command Syntax show bluetooth Command Access Admin level only Example Switched CDU: show bluetooth Bluetooth Configuration Bluetooth: enabled Name: BT-Mod1 Pin code: 0000 Discoverability: enabled Transmission Power: 0 (dbm) show branches Shows branch configuration values. Command Syntax show branches Command Access...
Page 182
show cords Shows cord configuration values. Command Syntax show cords Command Access Admin level only Example Switched CDU: show cords Cord Name --------- Master_Cord_A Link_Cord_A SNMP Email User / Factory User / Factory Notif. Notif. Current Capacity Nominal Voltage ------ ------ ---------------- ---------------...
show features Shows the enabled system features. Command Syntax show features Command Access Admin level only Example Switched CDU: show features Add-on features installed on this system: Smart Load Shedding show ftp Shows FTP configuration values. Command Syntax show ftp Command Access Admin level only Example...
Page 185
show ldap Shows LDAP configuration values. Command Syntax show ldap Command Access Admin level only Example Switched CDU: show ldap LDAP Configuration LDAP: disabled Primary Host: <not set> Secondary Host: <not set> Port: Bind Type: Simple Search Bind Password: <not set> User Search Base DN: Filter:...
Page 186
show lines Shows line configuration values. Command Syntax show lines Command Access Admin level only Example Switched CDU: show lines Line Name --------- AA:L1 CA:L1 DA:L1 SNMP Email Current Current Current Current Notif. Notif. Current Lo-Alrm Lo-Warn Hi-Warn Hi-Alrm ------ ------ ------- -------...
Page 187
show loadshed Shows load shedding configuration values. Command Syntax show loadshed Command Access Admin level only Example Switched CDU: show loadshed General load shedding options: Status Action Delay UPS On-Battery Load Shedding: disabled 0 minute(s) UPS On-Utility Auto Recovery: enabled 0 minute(s) Line Load Shedding: disabled...
Page 188
show log Shows the system event log. Command Syntax show log [filter] Parameters The show log command uses the following parameter: filter Keyword filter for long entries. Command Access Admin level only Example Switched CDU: show log There are 8 messages in the system log (#1-#8) [1] L6 EVENT: Network stack started [2] L6 EVENT: System boot complete [3] L2 EVENT: High alarm (temperature 22.9C) detected on temperature sensor 'Temp_Sensor_C2' [C2]...
show sensors Shows sensor configuration values. Command Syntax show sensors Command Access Admin level only Example Switched CDU: show sensors Sensor Sensor Name ------ ----------- Temp Temp_Sensor_A1 Temp Temp_Sensor_A2 Temp Temp_Sensor_C1 Temp Temp_Sensor_C2 Humid Humid_Sensor_A1 Humid Humid_Sensor_A2 Humid Humid_Sensor_C1 Humid Humid_Sensor_C2 Contact C1 Contact_Sensor_C1...
Page 195
show shutdown Shows outlet shutdown configuration values. Command Syntax show shutdown Usage Guidelines This command is for Switched products only. Command Access Admin level only Example Switched CDU: show shutdown Outlet Name Shutdown/Delay Script/Delay ----------- -------------- ------------ Master_Outlet_1 Off / 90 sec Off / 1 min Master_Outlet_2 Off / 90 sec...
Page 196
show snmp Shows SNMP configuration values. Command Syntax show snmp Command Access Admin level only Example Switched CDU: show snmp SNMP Configuration SNMPv2 Agent: enabled Get Community <RO>: public Set Community <RW>: SNMPv3 Agent: disabled Engine ID: 8000006B602 RW User Name: <not set>...
show system Shows system uptime, firmware version, firmware build information, boot version, hardware version, number of active users, and location string. Command Syntax show system Command Access Admin level only Example Switched CDU: show system System Information Uptime: 1 day 20 hours 0 minutes 13 seconds Firmware: Sentry Switched CDU Version 8.0a Build Info:...
Page 199
show units Shows CDU configuration values. Command Syntax show units Command Access Admin level only Example Switched CDU: show units Unit Name: Master <A> Type: Master Model Number: STV-6503K Product S/N: STVU0000118 Asset Tag: testtag1asdf Display Orient: Auto <Normal> Outlet Sequence: Normal SNMP Notif.: enabled Email Notif.:...
Page 200
show waps Description: Displays the available wireless access points. Command Syntax: show waps Command Access: Admin level only; wireless module installed. show wlan Description Displays the wireless network configurations. Command Syntax: show wlan Command Access: Admin level only; wireless module installed. Switched PRO2 –...
Page 201
shutdown Turns off a specified outlet or outlet group after performing a user-specified shutdown operation. Command Syntax shutdown <name | id | group | ALL> Usage Guidelines For Switched CDU products only. Command Access Admin and Power User Example Switched CDU: shutdown Outlet name or ID, group name or ALL: status Displays the latest status and control state for a specified outlet or outlet group.
Page 202
sysstat Displays the count of all system objects (by type), the latest status of the objects, and the count of objects currently in an event condition. Command Syntax sysstat Command Access System Monitor access Example Switched CDU: sysstat Sub-System Status Events ---------- ------...
ustat Displays the latest status and metrics for all CDUs in the system. Command Syntax ustat Command Access System Monitor access Example Switched CDU: ustat Unit Name Type Status --------- ----- ------ Master Master Normal Display Orientation ------------------- Auto <Inverted> version Displays the current firmware version.
Appendix A: Product Support Information LED Indicators The following input current LED indicators can be displayed on the Switched PRO2 products: Behavior/Indicator Description Comments/User Action Occurs during normal boots, restarts, and firmware If the behavior is endless, contact Server “--” (flashing double dashes) flash updates but should revert to displaying Technology Technical Support at: amperage values upon completion.
Branch Circuit Protection Server Technology PDUs are equipped with one of several types of Branch Circuit Protection, including internal fuses, retractable fuse holders, and circuit breakers, as illustrated below. These fuses and circuit breakers meet the strict safety requirements of UL 60950-1 and EN 60950-1 for Branch Circuit Protection.
Compact Fuse Holder The Compact Fuse Holder is a UL 98 listed Fused Disconnect Switch that allows the user to turn OFF the branch circuit and safely service the fuse without having to disconnect the PDU AC power source prior to performing this operation.
Fuse Retractor, Fuse Access Window, and Fuse Access Cover The PDU AC power source must be disconnected prior to servicing a unit with the Fuse Retractor, Fuse Access Window, and Fuse Access Cover. Intelligent PDUs with branch circuit sensing will display a flashing FE on the input current LEDs to indicate Fault Error.
Experience Server Technology's FREE Technical Support Server Technology understands that there are often questions when installing and/or using a new product. Free Technical Support is provided from 8 a.m. to 5 p.m. PST, Monday through Friday. After-hours service is provided to ensure your requests are handled quickly no matter what time zone or country you are located in.
PROx Network Interface Card (NIC) Swap The NIC in your PROx PDU is a hot-swappable assembly that can be removed and installed without the loss of output voltage, as described in the following instructions: 1. Remove the Phillips-head retention screws and save for step 4. Note: Some models have either one or two screws, shown in the following two images: 2.
Appendix B: Regulatory Compliance Product Safety Units have been safety tested and certified to the following standards: USA/Canada UL 62368-1:2019 and CAN/CSA 22.2 No. 62368-1:2019 • • European Union EN IEC 62368-1:2020+A11:2020 IEC CB Scheme IEC 62368-1:2018 • This product is also designed for Norwegian IT power system with phase-to phase voltage 230V. Notifications USA Notification Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to...
Recycling Server Technology Inc. encourages the recycling of its products. Disposal facilities, environmental conditions and regulations vary across local, state and country jurisdictions, so Server Technology encourages consultation with qualified professional and applicable regulations and authorities within your region to ensure proper disposal.
Fax: 775-284-2065 Email: support@servertech.com Return Merchandise Authorization (RMA) If you have a product that is not functioning properly and needs technical assistance or repair, see the Server Technology Return Merchandise Authorization process at: www.servertech.com Switched PRO2 – User Guide Appendix C: Product Warranty–Technical Support–RMA...