set outlet
Command Syntax
Parameters
Sub-Parameters
Command Access
Using the Command Line Interface (CLI)
Sets outlet configuration values.
set outlet email [disabled | enabled] <name | id | ALL>
set outlet load [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set outlet load hyst <value>
set outlet name <name | id> <new name>
set outlet snmpt [disabled | enabled] <name | id | ALL>
set outlet watts [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set outlet watts hyst <value>
For AC products only:
set outlet pf [alarmlo | warnlo] <name | id | ALL> <value>
set outlet pf hyst <value>
The set outlet command uses the following parameters:
email
Sets email notifications for outlet events.
hyst
Sets the hysteresis between event state and recovery.
load
Sets the current load for an outlet. min 0.0A, max (max current) in
show outlets command, hyst 0.0-10.0A (default 1.0A)
pf
Sets the power factor. min 0.00, max 1.00, hyst 0.0-0.20 (default 0.02)
snmpt
Sets if SNMP trap notifications for outlet events.
watts
Sets the power (without power factor). min 0W, max (power capacity) in
ostat, hyst 0-1000W (default 10W).
The set outlet command uses the following sub-parameters:
alarmhi
Sets high alarm value.
alarmlo
Sets low alarm value.
warnhi
Sets high warning value.
warnlo
Sets low warning value.
min <= alarmlo <= warnlo <= warnhi <= alarmhi <= max
Admin level only
Smart PRO2 – User Guide
•
162