Configuring Humidity Sensors Thresholds
Click the humidity sensor thresholds link at the bottom of the Sensors page to display the configuration page:
To set humidity sensor thresholds:
1. Provide the threshold hysteresis between event state and recovery (%RH). Range is 0-20% RH; default is
2% RH.
2. Set the low/high alarm and low/high warning threshold values for the humidity sensor (%RH). Range is min
0% RH, max100% RH.
3. Click Apply.
Using the Web Interface