Configuring 3-Phase Out-Of-Balance Thresholds
Click the out-of-balance link at the bottom of the Cords page to display the configuration page:
To set out-of-balance factor thresholds:
1. Provide a percent for threshold hysteresis between event state and recovery. Range is 0-10%; the default
is 2%.
2. Set percent for high warning/alarm out-of-balance thresholds. Range is min 0%; the max is 200%.
3. Click Apply.
Notes:
Out-of-balance is the percent power difference between phases of a cord.
•
•
When a device with 3-phase input voltage is out-of-balance, efficiency is reduced and the unit is
prevented from reaching maximum capacity, making it necessary to adjust distribution of the loads.
Using the Web Interface
Smart PRO2 – User Guide
•
55
Need help?
Do you have a question about the PRO2 Switched POPS C2WG12BM and is the answer not in the manual?