Battery Mode Start-Up Procedures - Delta Ultron Series User Manual

Three phase 300-600 kva
Hide thumbs Also See for Ultron Series:
Table of Contents

Advertisement

6.2.2

Battery Mode Start-up Procedures

WARNING: 
Before turning on the UPS, please read 6.1 Pre Start-up & Pre Turn-off Warnings
thoroughly and ensure that the precautions and instructions have been followed.
Step 1
Ensure that the Manual Bypass Switch (Q3) is in the OFF position.
Step 2
Switch ON every external battery cabinet's breaker (Q5).
Step 3
Switch ON the Output Switch (Q4).
Step 4
Press any of the BATT. START buttons on the communication interfaces I for one second.
Step 5
Tap the ON/ OFF Button (
Step 6
After the inverter turns on, the UPS will run in Battery mode, the LCD screen will show as
below, and the tri-color LED indicator will illuminate yellow.
) on the LCD screen.
103