6.
Single Input: Switch OFF the bypass breaker, input breaker and output breaker.
Dual Input: Switch OFF the bypass breaker, input breaker and output breaker.
7.
The UPS will discharge DC bus voltage, and the tri-color LED indicator will illuminate yellow.
After discharging is completed, the UPS will shut down, and the touch panel and the tri-color
LED indicator will be off.
8.
Switch OFF every external battery cabinet's breaker.

6.3.7 Energy Recycle Mode Turn-off Procedures

WARNING:
1.
Energy mode is just for UPS aging test, and is only applicable for single unit
single input. The output does not need to take any load.
2.
In energy recycle mode, the charger is turned off.
1.
In energy recycle mode, the touch panel shows the following screen and the tri-color LED
indicator illuminates green.
(Figure 6-41: Energy Recycle Mode Screen)