7
Now, each power module performs DC BUS discharging and its LED indicator flashes
green. After discharging, each power module's LED indicator will be off.
8
About 3 minutes later, the UPS will shut down. After that, the LCD and the tricolor LED
indicator will be off.
9
Switch OFF every external battery cabinet's breaker (Q5).
6.3.7 Green Mode Turn-off Procedures
WARNING:
1. For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
2. For parallel application, if you just want to operate a specific UPS but not all
parallel ones, please contact service personnel.
1
In green mode, the LCD shows the following screen (Figure 6-62) and the tri-color
LED indicator illuminates green. For the tri-color LED indicator location, please refer to
Figure 2-11.
UPS-1.1
Power Flow
Power Flow
Summary
System Status
2
Press the ON/ OFF button (
if you want to power off the UPS's inverter. Please select 'YES'.
MEASUREMENT
SETUP
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
(Figure 6-62: Green Mode Screen & ON/ OFF Button Location)
MAINTENANCE
LOG IN
EVENT LOG
User
) once and the following screen will pop up to ask you
6-45
6
UPS Operation
10:15
May 25,2018
Green
ON/ OFF
Button
Load
30 %