Removing and replacing the energy pack
Removing and replacing the energy pack
About this task
About this task
CAUTION:
CAUTION:
A discharge of static electricity from a finger or other conductor might damage system boards or other static-sensitive
devices. To prevent damage, observe antistatic precautions.
Procedure
Procedure
1. Power down the server.
2. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
3. Disconnect all peripheral cables from the server.
4. Do one of the following:
If the server is in tower mode, place the server on a flat, level surface with the access panel facing up.
If the server is in rack mode, remove the server from the rack .
5. Remove the access panel .
6. If installed, remove the air baffle .
7. Remove the energy pack:
a. Disconnect the energy pack cable (callout 1).
b. Press and hold the rear latch (callout 2), and then lift the rear end of the energy pack from the holder (callout 3).
c. Remove the energy pack from the holder (callout 4).
HPE ProLiant ML30 Gen10 Plus Server Maintenance and Service Guide
90