7 .
Install wiring between the UPS and RMP II. See Figure 5-2 and Table 5-1 for the Powerware Hot Sync
CAN Bridge Card terminal location and wiring information, and Figure 5-7, Figure 5-8, and Table 5-5 for the
RMP II terminal location and wiring information.
NOTE
120 Vac for the RMP II should be supplied from the critical bus by facility planners or
the customer.
8.
Install 120 Vac power wiring from the critical bus to the RMP II. See Figure 5-7, Figure 5-8, and Table 5-5
for the terminal location and wiring information.
9.
Close the front door and secure the latch.
10. If removed, reinstall the safety shield panel removed in paragraph 5.1, Step 5. Secure with the retained
hardware.
11. If removed, reinstall the left front panel removed in paragraph 5.1, Step 4 and secure with the retained
hardware.
12. Restart the UPS. See Chapter 7, "UPS Operating Instructions" for startup instructions.
Terminal TB1
Signal Connections
from the UPS

Figure 5-7. Remote Monitor Panel II and Remote Monitor Panel II Terminal Locations

TM
Power Xpert
9395 550/275 UPS (225–550 kVA) Installation and Operation Manual 164201716—Rev 8 www.eaton.com/powerquality
Installing Options and Accessories
Ground
Terminal
Terminal TB3
120 Vac Power
5-9