Bell/PGM Support
PGMs must be assigned to one or more partitions. See section [007] for partition assignment.
Note: Bell PGM type requires supervision and follows arming squawks by partition.
Communications
Account codes are assigned to all system and partition events.
For SIA communications, a single account code (programmed in section [310][000]) is used for all events. The partition is
identified via Nri1-8. System events use Nri0.
When using communication formats other than SIA, individual account codes must be programmed for each partition. See "
[310] Account Codes" on page 126
Assign Zones
Partition zone assignments are completed using sections [201] - [208] for partitions 1 - 8. Subsections [001 - 016] are then
used to enable or disable banks of 8 zones on the partition.
Assign Users
Access [*][5] using the master code, select the desired user code and enter digit 4 to modify the partitions that can accept the
user code.
Factory Defaults
Individual modules, as well as the alarm panel itself, can have their programming returned to factory default settings. Hard-
ware is defaulted via the following Installer Programming sections:
[991] Default Keypads
l
000 – Default all keypad programming
l
001-016 – Default keypads 1-8
l
[996] Default wireless receiver
l
[998] Default HSM2955
l
[999] Default system
l
See "Defaults" on page 156 for more information.
Default All labels
Use programming section [000][999]. The following labels are returned to factory default settings:
Zone Label
l
Partition Labels
l
Module Labels
l
Partition 1-8 Command Output 1 to 4 Labels
l
Schedule 1 to 4 Labels
l
Event Labels
l
User Labels
l
System and module programming is not affected.
Hardware Reset Main Control Panel
Perform the following to restore the main control panel to default settings:
1. Power down the system.
2. Remove all wires between Zone 1 and PGM 1 on the alarm controller.
3. Connect a short between Zone 1 and PGM 1.
4. Power up the system for 60 seconds.
5. Power down the system and remove the short.
6. Power up the system again. Factory defaults are restored and hardware default is logged to the event buffer.
Note: Hardware default is not available when installers lockout is enabled.