[005] System Toggle Options
[1] Ethernet Receiver 1 Supervised Default (OFF)
ON: Ethernet receiver 1 will be supervised and heartbeats will be sent to Ethernet receiver 1 based on the super-
vision interval programmed in section [004].
OFF: Ethernet receiver 1 will not be supervised. When disabled, heartbeat 1 is sent to the Ethernet receiver once
every hour, regardless of supervision type (heartbeat 1 or 2). The heartbeat is resent every 5 seconds until ACK is
received. If no event or heartbeat ACK is received after (receiver supervision interval + 75 seconds), supervisory
trouble is indicated.
Note: Ethernet receiver 2 can not be supervised.
[2] Cellular Receiver 3 Supervised Default (OFF)
ON: Cellular receiver 3 will be supervised and heartbeats will be sent to cellular receiver 1 based on the supervision
interval programmed in section [004]. If ACK to heartbeat is not received, it is retransmitted every 5 seconds. Failure
to ACK two consecutive heartbeats will reset the radio.
OFF: Cellular receiver 3 will not be supervised. When disabled, heartbeat is not sent to the receiver. Supervisory
trouble is indicated.
Note: Cellular receiver 2 can not be supervised.
[3] Supervision Type Default (OFF)
ON: Heartbeat 1 (commercial supervision). This supervision type is suitable for applications where swap detection is
required on the supervisory packet.
OFF: Heartbeat 2 (residential supervision). This supervision type is suitable for applications where supervision of the
communication path to the receiver is required (no swap detection).
Note: Commercial supervision is more data intensive than residential supervision and should only be used when required
to meet the approval for the installation.
[4] Primary Path Default (OFF)
ON: Cellular channel is the primary path. Ethernet channel is the secondary path.
OFF: Ethernet channel is the primary path in a dual communicator. Cellular channel is the secondary path.
[6] Remote Firmware Upgrade Default (ON)
ON: The control panel firmware can be remotely upgraded using the Ethernet/cellular paths.
OFF: The control panel firmware can not be remotely upgraded. Local firmware upgrade is still possible.
[7] Alternate Test Transmissions Default (OFF).
ON: When the periodic test transmission interval occurs, the test transmission will alternate between being sent to the
primary and secondary receivers with each test transmission interval.
OFF: When the periodic test transmission interval occurs, the test transmission will be sent to the programmed receiv-
ers, based on the settings of the periodic test transmission reporting codes.
[8] Cellular Low Signal Trouble. Default (OFF)
This option masks the low signal trouble from generating cellular trouble.
ON: A cellular trouble event is generated when the radio signal level falls below threshold level (average CSQ level
is 4 or less).
OFF: A cellular trouble event is not generated when the radio signal level falls below threshold level (average CSQ
level is 4 or less).
[006] System Toggle Options 2
[1] Ethernet 1 receiver enabled. Default (ON)
ON: Ethernet receiver 1 is enabled.
OFF: Ethernet receiver 1 is disabled.
[2] Ethernet receiver 2 is enabled. Default (ON)
ON: Ethernet receiver 2 is enabled.
OFF: Ethernet receiver 2 is disabled.
[3] Reserved
Section 5: Programming
- 137 -
Need help?
Do you have a question about the tyco Power Pro Series and is the answer not in the manual?