Section 5: Programming
The account code is used by the central station to distinguish between transmitters. This account code is used when trans-
mitting heartbeat signals to the central station receiver. Signals received from the control panel will use the control panel
account number. Valid range: 0000000001 - FFFFFFFFFE.
[202] Cellular Receiver 3 DNIS
Default (000000)
The DNIS is used in addition to the account code to identify the communicator module at the central station. Valid range:
000000 - 0FFFFF Values are entered as a leading 0 followed by the 6-digit DNIS.
Note: Each Ethernet/cellular receiver must be programmed with a unique DNIS.
[203] Cellular Receiver 3 IP Address
Default (000.000.000.000)
Enter the cellular receiver 1 IP address. This information will be provided by the central station system administrator. Each 3-
digit segment of the address must be within a valid range of 000-255.
Note: When a valid IP address has been entered, the cellular receiver is enabled and will communicate events over the cel-
lular channel.
[204] Cellular Receiver 3 Port
Default (03061)
This section determines the port used by cellular receiver 3. Change the default value of this port when the installation is loc-
ated behind a firewall and must be assigned a particular port number as determined by the central station system admin-
istrator. Valid range: 00000 - 65535.
Note: Programming this section with 00000 will disable the receiver.
[205] Cellular Receiver 3 APN
Default ()
The Access Point Name (APN) determines the cellular network that the communicator will connect to. This information is
available from the network carrier. Program this section as 32 ASCII characters.
Note: When a SIM card with a custom APN is used, the unit will not have access to the Internet. DLS and remote flash can
still be done if section [221] is programmed with a valid public APN.
[206] Cellular Receiver 3 Domain Name
Default (   )
Enter the Domain Name as 32 ASCII characters. This information will be provided by the central station system admin-
istrator.
Cellular Receiver 4 Options
[211] Cellular Receiver 4 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between different transmitters. This account code is used when
transmitting signals to the central station receiver. Signals received on the panel will use the panel account number. Valid
range: 0000000001 - FFFFFFFFFE.
[212] Cellular Receiver 4 DNIS
Default (000000)
The DNIS is used in addition to the account code to identify the communicator module at the central station. Valid range:
000000 - 099999. Values are entered as a 0 followed by the 6-digit DNIS value. Format is BCD.
Note: Each Ethernet/cellular receiver must be programmed with a unique DNIS.
[213] Cellular Receiver4 IP Address
Default (000.000.000.000)
Enter the cellular receiver 4 IP address. This IP address will be provided by the central station. Format is 4 fields, each field
is 3-digit decimal. Valid range: 000 - 255.
Note: When a valid address has been entered, cellular receiver 2 is enabled and will communicate events over the cellular
path.
[214] Cellular Receiver 4 Port
Default (03061)
- 144 -