043
24-Hour Panic
Instant alarm when activated, audible alarm at default.
045
24-Hour Heat
Instant alarm when activated, audible alarm at default.
046
24-Hour Medical
Instant alarm when activated, audible alarm at default.
047
24-Hour Emergency
Instant alarm when activated, audible alarm at default.
048
24-Hour Sprinkler
Instant alarm when activated, audible alarm at default.
049
24-Hour Flood
Instant alarm when activated, audible alarm at default.
051
24-Hour Latching Tamper
Instant alarm when activated, audible alarm at default. The alarm system cannot be armed until Installer Programming is
entered after the zone is restored.
052
24-Hour Non-Alarm
This zone is active at all times but does not cause an alarm. Zone attributes such as Zone Bypassing and Door Chime affect
the functionality of this zone. This zone type can also be assigned to a temperature sensor if indoor/outdoor temperature dis-
play is required without temperature warnings or alarm conditions.
056
24 Hour High Temperature
This zone type is used with wireless temperature sensors and is activated when the temperature rises above a programmed
threshold (set in section [804][xxx][019-020]). Instant alarm when activated, audible alarm at default. This zone type gen-
erates an alarm when the system is armed or disarmed.
Note: This zone type cannot be used on hardwired zones. The temperature threshold includes a 3 °C (5-6 °F) difference
between a given state and its restored condition. For example, an alarm at 6 °C is restored at 3°C (High temperature) or 9°C
(Low temperature), depending upon the zone type selected.
The zone type for wireless temperature sensors must be 24 Hour High/Low Temperature in order for the sensor to operate
properly.
057
24-Hour Low Temperature
This zone type is used with wireless temperature sensors and is activated when the temperature drops below a programmed
threshold (set in section [804][xxx][019-020]). Instant alarm when activated, audible alarm at default. This zone type gen-
erates an alarm when the system is armed or disarmed.
Note: This zone type cannot be used on hardwired zones.
060
24-Hour Non-Latching Tamper
This zone is always active and reports a tamper condition with no audible alarm when opened or tamper/faulted.
061 - 24-Hour Masking
This zone is active 24 hours in either the armed or the disarmed state. This zone type does not generate an alarm, and does
not log in the Alarm Memory. This zone type generates a Masking Trouble on the system.
Note: This zone operates in SEOL only.
066
Momentary Keyswitch Arm
Often used with a keyswitch module*, turning the key alternately arms and disarms the system and silences the alarms.
Tampers and faults only initiate their respective trouble sequence. The keypad gives no indication when this zone type is
activated.
Note: With audible alarm active, using the keyswitch when disarmed is the same as entering an access code at the keypad.
Using the keyswitch during the first 30 seconds of a delayed fire alarm is the same as pressing a key at the keypad (the 90
second delay starts). Activation of a keyswitch zone arms or disarms the system. Activation of this zone type is NOT logged
nor is the Police code transmitted. Bypassed zones of this type are not un-bypassed when the system is disarmed. When the
zone is bypassed, a zone bypass event buffer log and communication occurs immediately, NOT when the system is armed.
*Keyswitch module not for use in UL/ULC listed installations.
Section 5: Programming