[024] System Option 12
1 – Reserved
2 – Reserved
3 – AC/DC Inhibits Arming
EN
ON: The system cannot be armed when an AC or battery trouble is present. This includes keypad, keyswitch, automatic, and
DLS arming. An error tone is generated if the user attempts to arm the system during an AC/DC trouble.
Note: Displaying AC troubles ([016] option 2) is strongly recommended if this option is enabled.
OFF: The system can be armed, regardless of the presence of an AC or DC trouble and does not check the system battery
upon arming.
4 – Tampers Inhibit Arming
EN
ON: The following conditions trigger Tampers Inhibit Arming:
Faults on the zones, modules
l
Tampers on the zones, modules
l
Bell circuit trouble
l
Communications fault troubles (TLM, FTC, Radio/Sim card failure, ethernet trouble, communicator fault)
l
Warm start troubles
l
Tampers must be restored through Installer Programming before the system can be armed (including no-activity and key-
switch arming). Reset Required displays on the keypad.
When this option is enabled, manual zone bypassing does not bypass the tamper or fault states (DEOL). This feature also
applies to zone faults.
OFF: Tamper troubles do not latch and do not prevent arming.
5 – Real time Clock
ON: If enabled, the panel will set the time and date automatically provided by either the on board Ethernet or the cellular com-
municator at 4:05pm.
OFF: If disabled, the system time and date needs to be manually programmed
Note: The time zone of the panel must be set in [851][020] and the Ethernet or Cellular communication must be com-
municating to a System 5 Surgard receiver.
6 – Reserved
7 – Reserved
8 – DLS Disconnect
ON: All events except Periodic Test Transmission, Periodic Test with Trouble, and System Test are considered priority
events. If DLS is active when an event occurs, the alarm system immediately terminates the connection in order to com-
municate the new events.
OFF: Only the following alarm type events terminate a DLS session:
Zone alarms
l
FMP key alarms
l
Duress alarms
l
Zone expander supervisory alarms
l
2-wire smoke alarms
l
[025] System Option 13
1 – European Dial
ON: Pulse dialing make/break ratio is 33/67.
OFF: Pulse dialing make/break ratio is 40/60.
2 – Force Dial
ON: The system dials the central station phone number even if no dial tone is present. The process is as follows:
1. Dial programmed phone number.
2. If no dial tone detected, terminate call.
3. Search for dial tone for 5 seconds.
Section 5: Programming
- 115 -