SYSTem[:COMMunicate]:BOOL[:STATe] <DSC>
Function
Select query Return format of Boolean (<Bool>) commands.
DIGIT – Boolean queries are replied with 0|1.
TEXT – Boolean queries are replied with OFF|ON.
Parameters
DIGIT|TEXT or 0|1
Query
SYSTem[:COMMunicate]:BOOL[:STATe]?
Return
<DSC> DIGIT, TEXT
SYSTem[:COMMunicate]:BOOL[:STATe] <DSC> command is available from firmware revision
02.110.
SYSTem[:COMMunicate]:INTerface <DSC>
Function
Sets a communication interface.
Power supply addressing is lost after communication interface change.
Parameters
0|1|2|3|4, RS232|RS485|LAN|USB|OPTion
Query
SYSTem[:COMMunicate]:INTerface?
Return
<DSC> RS232, RS485, LAN, USB, OPT
Execution time for this command is ~25mS
SYSTem[:COMMunicate]:LAN:HOST?
Query
Reads hostname. LAN specific command.
Return
<SRD> up to 15 characters long
Example
G10-500-<X>
<X> represents a running number (1, 2, 3, etc.) according to the number of Power Supplies from
the same type.
A number is added only if at least 2 Power Supplies of the same type are connected to the same
network.
SYSTem[:COMMunicate]:LAN:IDLED <Bool>
Function
Blink Display & green LXI LED. LAN specific command.
Parameters
0|1, OFF|ON
NOTE
NOTE
NOTES