[PROGram]:STORe <NR1>
Function
Stores a sequence in a specified memory cell 1, 2, 3, or 4.
Stored parameters: mode, voltage/current, dwell/time, step, and counter.
Parameters
1|2|3|4
A delay of ~100mSec is required after the STORE command, before sending any additional
command.
[PROGram]:WAVE:CURRent <NRf+>,{<NRf+>}
Function
Specifies output current points in a wave.
Current points are separated by commas.
The function accepts up to 100 parameters.
Parameters
The range is limited by the power supply current programming range.
Unit
A
Query
[PROGram]:WAVE:CURRent?
Return
<NR2>,{<NR2>} 5-digits format
Example
WAVE:CURR 2.5,3.0,3.5; WAVE:CURR MAX,2.5,MIN;
A delay of ~100mSec is required after the [PROGram]:WAVE:CURRent command if long
sequences are used, before sending any additional command.
[PROGram]:WAVE:TIME <NRf+>,{<NRf+>}
Function:
Specifies the time interval of each slope between 2 points of a WAVE.
The function defines up to 100 parameters.
Parameters
0.001–129,600 seconds. Default: 0.001s
Unit
S
Query
[PROGram]:WAVE:TIME?
Return
<NR2>,{<NR2>}
Example
WAVE:TIME .6,1.5,1.5,.4
A delay of ~100mSec is required after the [PROGram]:WAVE:TIME command if long sequences
are used, before sending any additional command.
NOTE
NOTE
NOTE