[SOURce]:VOLTage:PROTection:LOW:STATe <Bool>
Function
Enables/Disables the under voltage protection (UVP) mode.
If enabled, the output is disabled when measured output voltage reaches
the UVL level.
UVP bit is set in the Questionable Condition register.
Parameters
0|1, OFF|ON
Query
[SOURce]:VOLTage:PROTection:LOW:STATe?
Return
<Bool> 0|1
UVP function is disabled if under voltage limit setting is below 5% of the rated power supply
voltage.
[SOURce]:VOLTage:PROTection:LOW[:LEVel] <NRf+>
Function
Sets the under voltage limit level.
Parameters
The range is limited by the UVL programming range and voltage
programmed value.
Unit
V
Query
[SOURce]:VOLTage:PROTection:LOW:LEVel?;
VOLTage:PROTection:LOW:LEVel? MIN; :VOLTage:PROTection:LOW:LEVel?
MAX
Return
<NR2> 5-digits format
UVL setting is 5% below the actual voltage setting.
[SOURce]:POWer:STATe <Bool>
Function
Enables/Disables the constant power limit mode.
Parameters
0|1, OFF|ON
Query
[SOURce]:POWer:STATe?
Return
<Bool> 0|1
Analog programming, internal resistance, sequencer, and Slew-Rate functions should be disabled
to enable Constant Power.
NOTE
NOTE
NOTE