*OPT?
Query
Returns the type of an optional card installed.
Returns
<SRD>
0,No Option Installed
1,GPIB
2,MODBUS
3,ETHERCAT
*PSC <Bool>
Function
The Power ON Status Clear (PSC) command controls automatic Power ON clear
of the Service Request Enable Register, the Standard Event Status Enable
Register, and Device Specific Event Enable registers.
ON (1) - Enables the Power ON clear of the listed registers (default).
OFF (0) - Disables clear of the listed registers. Registers retain their status
when a Power ON condition occurs.
Parameters
0|1, OFF|ON
Query
*PSC?
Returns
<Bool> 0|1
*RCL <NR1>
Function
This command restores power supply to a state stored in the memory (locations
1 through 4), previously stored by the *SAV <NR1> command. Refer to Section
2.13.5
Parameters
1,2,3,4.
RCL without a parameter restores the power supply state stored in the memory
cell 1.
Execution time for this command is ~100mS
*RST
Function
Executes reset. Refer to Table 2-6
*SAV <NR1>
Function
Saves the power supply state to a specific memory location. Refer to section
2.13.4.
Parameters
1,2,3,4.
SAV without a parameter stores the power supply state in the memory cell 1.