6.7 Trend Records

6.7
Trend Records

Function Description

6.7.1
NOTE
i
i
This function is only available in SICAM P855.
The function Trend records ensures the acquisition and long-term monitoring of the voltage V
values during voltage changes. The function Trend records compares the 1/2-cycle RMS value calculated from
measured value with last recorded 1/2-cycle RMS value in every 1/2 cycle. If the difference exceeds or falls
below the Tolerance number, the new 1/2-cycle RMS value is recorded.
[dw_trend_rec_Vrms, 2, en_US]
Figure 6-25
Once the measuring interval ends, the next measuring interval starts automatically. You can set the following
parameters via the Web pages:
Tolerance number
Maximum recording interval
Table 6-20
Measured Quantities
Va
Vb
Vc
Vab
Vbc
Vca
Interfaces: protocols IEC61850, HTML
Conditions: 1/2 cycle, RMS values
144
Example for Voltage Changes
Recording and Evaluation
PQDIF
x
x
x
x
x
x
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
(1/2-cycle)
rms